Download Print this page

Mitsubishi Electric P-RCC-E Installation Manual page 4

Lossnay heat recovery ventilator system component rc cover

Advertisement

5. Installation method (Continued)
4) Store the cable with noise filter along with the side face of the
control box as shown and pass the cable through the code bush.
Note:
- Do not pass the cable with noise filter through bushes other
than the bush shown below.
- Place the noise filter in the gap with the circuit board of the
controller box.
- Pull out the cable with noise filter until the packing touches
the bush.
Insert the cutting
Bush
Bush
5) Install the insulating sheet on the control box.
Insert the control box to the unit, attach two screws. (Don't
forget to place the insulating sheet)
Bind the cable with noise filter with a cable strap (supplied
with the unit) and attach it under the unit. (It is recommended
to install it with flexibility so that it will not be loaded from the
outside.)
Screw
Install the remote controller.
1) Loosen the two screws from the terminal block and remove
the terminal cable from the bottom case.
2) Connect the remote controller cable (field supplied) to the
terminal block on the bottom case.
Peel off 6 mm of the remote controller cable sheath as shown
in the figure below, and thread the cable from behind the
bottom case. Thread the cable to the front of the bottom case
so that the peeled part of the cable cannot be seen behind
the bottom case. Connect the remote controller cable to the
terminal block on the bottom case.
Manufactured by:
TOKYO BLDG. 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO, 100-8310 JAPAN
Noise filter
Control box
Packing
Cable with noise filter
Control box
Cable strap
Terminal cable
Terminal block
Screw
Thread the sheath part
of the cable to the front.
Sheath
10 (13/32)
Front
Back
6 (1/4)
Unit: mm(in)
Thread the cable.
3) Install the bottom case.
- Thread the cable through the groove.
- Secure at least two corners of the remote controller with
screws.
- Be sure to secure top-left and bottom-right corners of the
remote controller (viewed from the front) to prevent it from
lifting.(Use molly anchor etc.).
Wood screw for direct wall
installation or Roundhead
cross slot screw for switch
box installation
4) Cut out the cable access hole.
■ Direct wall installation (when running the cable along the wall)
- Cut out the thin-wall part on the cover
(indicated with the shaded area in the
right figure) with a knife or a nipper.
- Thread the cable from the groove
behind the bottom case through this
access hole.
5) Install the front cover on the bottom case.
Hook the two tabs onto the bottom case. Check that the front
cover is securely installed and not lifted.
■ Direct wall installation (when running the cable along the wall)
- Thread the cable through
the access hole at the top of
the remote controller.
- Seal the cut-out part of the
cover with putty.
- Use a cable cover.
6) Wire the cable with noise filter and the remote controller
cable.
2-core wire must not
be seen on the back.
Connect the cable.
(non-polarized)
Connect the cable so that the
cable sheath is not pinched.
Remote controller cable
Refer to 2).
Thread the cable through
the groove.
Wall
No lifting
Seal the gap with putty.
Use a cable cover.
Thread the cable through the
top of the remote controller.

Advertisement

loading