Download Print this page

Mitsubishi Electric P-RCC-E Installation Manual page 2

Lossnay heat recovery ventilator system component rc cover

Advertisement

2. Outside dimensions
63.2
3. Field-supplied parts/Required tools
(1) Field-supplied parts
The following parts are field-supplied parts.
Parts name
Double switch box
Thin metal conduit
Lock nut and bushing
Cable cover
Putty
Molly anchor
Remote controller cable
(Use a 0.3 mm² (AWG22) 2-core sheathed cable.)
(2) Field-supplied tools
- Flat-tip screwdriver (Width: 4-7 mm (5/32-9/32 inch))
- Knife or Nipper
- Miscellaneous tools
4. Selecting an installation site
This remote controller is for the wall installation. It can be installed either in the switch box or directly on the wall. When performing
direct wall installation, wires can be thread through either back or top of the remote controller.
(1) Selecting an installation site
To prevent injury, install the controller on a flat surface strong enough to support its weight.
Important
To reduce the risk of shorting, current leakage, electric shock,
malfunctions, smoke, or fire, do not install the controller in a
place exposed to water or in a condensing environment.
(2) Installation space
Leave a space around the remote controller as shown in the figure at right,
regardless of whether the controller is installed in the switch box or directly
on the wall. Removing the remote controller will not be easy with insufficient
space. Also, leave an operating space in front of the remote controller.
120
19
18.4
40
Unit: mm
Not required for direct wall installation
Required for routing remote controller cable along a wall.
Total wiring length is up to 200 m.
Accessories
Wood screw (4.1 X 16): 2
Cable with noise filter: 1
(Cable length outside the prod-
uct: Approximately 820 mm)
Notes
To avoid deformation and malfunction, do not install the remote
controller in direct sunlight or where the ambient temperature
may exceed 40ºC (104ºF) or drop below 0ºC (32ºF).
To reduce the risk of malfunctions and damage to the controller,
avoid installing the remote controller on an electrically
conductive surface, such as an unpainted metal sheet.
Minimum required space
around the remote
controller
2
Roundhead cross slot screw
(M4 X 30): 2
Terminal protective cap: 1
External dimensions of remote
controller
30 (1-3/16)
30
30
(1-3/16)
1-3/16
(
)
120 (4-3/4)
120 (4-3/4)
120 (4-3/4)
Unit: mm (inch)

Advertisement

loading