Electrical control installation
Specifications of wiring
Notes:
•
•
•
Electrical parameters of outdoor unit
Frequency
Model
Hz
TX(U)M524AMAA
TX(U)M536AMAA
50
TX(U)M542AMAA
TX(U)M548AMAA
TX(U)M548ADAA
50
DIP setting for the controller of outdoor unit
SW1 (upper DIP)
SW2 (lower DIP)
30
Flexible wire is recommended because the wire needs to be bent during installation, otherwise
it will produce installation problem.
Data in the following table only correspond to the stranded copper core fl exible wire. If other
wire will be chosen, please refer to the electrical engineering handbook in accordance with the
wiring current provided in the table.
For the safety of the unit, wiring shall not be based on the rated current, because the operating
conditions will change with the season.
Maximum
Lower
Upper
Rated
limit of
limit of
current of
voltage
voltage
voltage
compressor
V
V
V
220
~
198
264
240
380
342
418
Outdoor unit capacity
DIP
S1
S2
S3
Outdoor unit
System connecting pipe
address DIP
length correction
S1
S2
S3
S4
start
Rated
Rated
current of
current of
compressor
fan motor
MSC
RLA
FLA
(A)
(A)
(A)
11.4
11.4
0.6
14.5
14.5
0.6
20
20
1.2
23
23
1.2
8
8
1.2
Indoor unit quantity DIP
S4
S5
S6
Cooling
only/Heating
pump
S5
S6
Recommended
Minimum
specification of
specification
line current
fuse
MCA
RDE
(A)
(A)
21
25
22
25
27
30
31
35
11
14
Limit of cooling and heating
temperature range
S7
Assigned
Indoor unit address
address mode
S7
Minimum
diameter
Maximum
specification
of the
of fuse
copper core
MFA
wire
2
(A)
mm
35
4
35
4
50
6
55
6
20
2.5
Forced
cooling
S8
setting way
S8