Assembly instruction for SBE160, SBE320, SBX175 and SBX350 Series two pole battery connectors with option for
auxiliary contacts.
FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND
LOCAL ELECTRICAL CODES AND THE FOLLOWING INSTRUCTIONS. THE SUITABILITY OF
THIS TYPE OF TERMINATION MUST BE EVALUATED BY UNDERWRITERS' LABORATORIES,
INC. AND CANADIAN STANDARDS. ASSOCIATION FOR THE END USE APPLICATION: Assemble
contacts to the cables according to the equipment manufacturer's assembly instructions. The following
instructions are supplied as a reference. Please note: instructions are included with each crimp tool
for proper use.
Contains one (1) housing and two (2) contacts.
1. CONNECTOR RATINGS
Series
Amperes
Volts
SBE160
160
150
SBE320
320
150
SBX175
175
600
SBX350
550
600
2. TOOLING CHART
Contact
Wire
Part Number
Size
6384G2
35 mm²
6384G1
1/0 AWG
6354
2/0 AWG
6354
2/0 AWG
6355
3/0 AWG
6356
4/0 AWG
6358
300 MCM
6358
350 MCM
1341G1
50 mm²
1341G2
70 mm²
1341G3
95 mm²
3. REDUCING BUSHING
Bushing
Wire Size
Part Number
AWG (mm²)
5687
#1 (42.4)
5690
#2 (33.6)
5693
#4 (21.2)
5663
#6 (13.3)
5648
#10 (5.3)
5920
N/A (16)
5918
1/0 (53.5)
®
350 Connectors
Max Cable Size
AWG
mm²
1/0
50
350 mcm 185
1/0
50
350 mcm 150
Pneumatic
Bench Tool + Die +
1387G1
1388G3
1387G2
1303G2
1387G1
1388G2
1387G2
1303G12 1304G28
1387G2
1303G12 1304G31
1303G12
1303G12 1304G31
N/A
N/A
N/A
N/A
1387G2
1303G8
1387G2
1303G7
1387G2
1303G12 1304G35
For Use With
SBE160 / SBX175
6384G1 contact
6384G1 contact
6384G1 contact
6384G1 contact
6384G1 contact
6384G2 contact
N/A
Dieless
Locator or Hydraulic Tool
1389G3
1368
1304G2
1368
1389G2
1368
1368
1368
1368
N/A
1368
N/A
1368
1304G35
1368
1304G27
1368
1368
SBE320 / SBX350
6354 contact + 5918 bushing
6354 contact + 5918 bushing
6354 contact + 5918 bushing
6354 contact + 5918 bushing
6354 contact + 5918 bushing
6394 contact
6354 contact

Advertisement

loading

Summary of Contents for IDEAL APP SBE 320

  • Page 1 ® ® 320 & SBX 350 Connectors Assembly instruction for SBE160, SBE320, SBX175 and SBX350 Series two pole battery connectors with option for auxiliary contacts. FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES AND THE FOLLOWING INSTRUCTIONS. THE SUITABILITY OF THIS TYPE OF TERMINATION MUST BE EVALUATED BY UNDERWRITERS’...
  • Page 2 4. CABLE STRIPPING DIMENSIONS FOR PRIMARY POWER CONTACTS Connector Strip “X” To Series Inches SBEX350 / SBE320 1 3/8 SBEX350 / SBE320 1 1/8 SBEX350 / SBE320 2 1/2 With 350MCM Cable CAUTION: When using cable with jacket diameter less than 0.423 inches (11mm) on the SBE160 / SBX175 and less than 0.709 inches (18mm) on the SBE320 / SBX350 thin wall heat shrink insulation should be evenly applied.
  • Page 3 7. CABLE / CONTACT & HOUSING ASSEMBLY Observing polarity of markings, push each contact into rear of housing until notched side snaps over spring, tug on cable to make sure contact is locked into place. DISASSEMBLING CONNECTORS (see illustration) Switch off power fi rst. Remove contact by inserting extraction tool (cat. no. SBE160 / SBX175 - 969P1, SBE320 / SBX350 - 970P1) as shown below (steps 1, 2, &...
  • Page 4 4. Thread or push one or two auxiliary contacts and wires through the rear of the connector before inserting into auxiliary housings. Push into auxiliary housings through rear until notched side of contact tip snaps over spring. Tug wires to make sure wires are secure. Figure 1 Retaining Pin Male Dovetail...

This manual is also suitable for:

App sbx 350App sbe160App sbx175