Page 1
® ® 320 & SBX 350 Connectors Assembly instruction for SBE160, SBE320, SBX175 and SBX350 Series two pole battery connectors with option for auxiliary contacts. FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES AND THE FOLLOWING INSTRUCTIONS. THE SUITABILITY OF THIS TYPE OF TERMINATION MUST BE EVALUATED BY UNDERWRITERS’...
Page 2
4. CABLE STRIPPING DIMENSIONS FOR PRIMARY POWER CONTACTS Connector Strip “X” To Series Inches SBEX350 / SBE320 1 3/8 SBEX350 / SBE320 1 1/8 SBEX350 / SBE320 2 1/2 With 350MCM Cable CAUTION: When using cable with jacket diameter less than 0.423 inches (11mm) on the SBE160 / SBX175 and less than 0.709 inches (18mm) on the SBE320 / SBX350 thin wall heat shrink insulation should be evenly applied.
Page 3
7. CABLE / CONTACT & HOUSING ASSEMBLY Observing polarity of markings, push each contact into rear of housing until notched side snaps over spring, tug on cable to make sure contact is locked into place. DISASSEMBLING CONNECTORS (see illustration) Switch off power fi rst. Remove contact by inserting extraction tool (cat. no. SBE160 / SBX175 - 969P1, SBE320 / SBX350 - 970P1) as shown below (steps 1, 2, &...
Page 4
4. Thread or push one or two auxiliary contacts and wires through the rear of the connector before inserting into auxiliary housings. Push into auxiliary housings through rear until notched side of contact tip snaps over spring. Tug wires to make sure wires are secure. Figure 1 Retaining Pin Male Dovetail...