All installations and services must be performed by qualified service personnel.
Heat Mode
When a call for heat ("W") is received from the thermostat, if the "Cool" mode is not already
active, the "T-T" terminal is energized and the blower on delay is started. The on-off pattern of
DIP switch SW2 (positions 1 and 2) select one of four blower on delay values (see Table 6).
When the delay time has elapsed, the "HEAT" blower speed is energized. The control remains
in steady heat mode until the thermostat is satisfied. When the call for heat signal is removed, the
"T-T" terminal is de-energized and the blower off delay is started. The on-off pattern of DIP
switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 8). When
the delay time has elapsed, the "HEAT" blower speed terminal is de-energized.
DIP SWITCH 2 SECTION
1
OF
OFF
F
ON
OFF
OF
ON
F
ON
ON
Table 7: ON and OFF Blower Delay Time Switch Settings
STATE
2
3
4
OFF
OFF
ON
OFF
OFF
ON
ON
ON
BLOWER DELAY TIMES
Counter
ON -
Flow
SEC
ON - SEC
15
30
24
60
36
120
48
240
14
OFF -
MIN
2
4
6
8