Page 1
SMOG-HOG Electrostatic Air Cleaner ® Owner’s Manual Model PSG...
Page 2
For quick future reference, fill in the unit information in the spaces below. Should you need assistance, call the Parker customer ser- vice number shown below. To expedite your service, have the following information avail- able when contacting Parker.
SAFETY PRECAUTIONS We have provided many important safety messages in this manual on your Smog-Hog PSG. Always read and obey all safety messages. This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and the word “DANGER”...
Page 7
Parker equipment should be by a licensed contractor that is also experienced in potential fire and explosion hazards and adheres to related local, state and federal codes, standards, laws and regulations. Parker is not an expert nor certified design consultant in relation to spark, fire or explosion mitigation including but not limited to detection, mitigation, suppression and isolation pf combustible dusts and materials.
Parker. Reading this manual is collecting components face the operator as air flows from left to important to the successful installation and operation.
Face & Overhead Wash Headers Outlet Odor Plenum Unicells Control System Inlet Blower Plenum Main Electrical Structural Panel Steel Skid Baffle Filters Power Pack Enclosures with Indicator Lights Wash Water Supply Pipe Connection Figure 2 PSG SERIES SYSTEM 1.4.2 Unicell Ionizer Section Each pack supplies power to a discrete module of unicells with Each unicell supports ten (10) 10 mil tungsten steel ionizer wires a dedicated, externally mounted indicator light that illuminates to...
Unit electrical panels provide the necessary electrical interlocks and controls for the PSG. If electrical control 2.3.4 Ducting panels supplied by others are not per Parker specifica- Quality ducting is important system performance. Sealed connec- tions the PSG is operating in an UNSAFE mode, voiding tions prevent air and liquid leakage during operation.
Be sure to inspect such items before mark- ing and storing. Open all cartons. Notify the trucking company and Parker immediately if cartons or any other shipping list items are missing. Handling SMOG-HOG skidded systems and subassem- blies are usually shipped to the job site on flatbed trailers.
For the PSG to operate at peak efficiency, certain pre-conditioning more), protect system components as follows: equipment may be required. When supplied by Parker, this equip- 1. Store in a cool, dry location. Do not disassemble. Do not re- ment should be installed per unit System Layout Drawing and unit move components.
Page 13
ENCOMPASSING DESIGN. APPROPRIATE DESIGN CRITERIA AS PROVIDED BY A PLUMBING/MECHANICAL CONTRACTOR SHOULD BE UTILIZED TO ENSURE PROPER CONTROL OF DRAINAGE EFFLUENT FROM THE SMOG HOG SYSTEM. PARKER ACCEPTS NO RESPONSIBILITY FOR THE PLUMBING DESIGN OR INSTALLATION. Figure 5 Drain Trap...
PSG system, indicating the er pack circuit to the Smog-Hog PSG and the system operational status of the In Place Cleaning System, (from BMS to exhaust blower.
Page 15
Figure 6 Unicell Electrical Alignment and Parts List REPLACEMENT PARTS QUANTITY ITEM NO. PART NO. DESCRIPTIONS REQUIRED 02-1921 UNICELL ASSEMBLY 36-0068 IONIZER CONTACT SPRING 30-0452 CONTACT WELD NUT 18-0674 IONIZER SUPPORT BAR (TOP) 18-0670 IONIZER SUPPORT BAR (BOTTOM) 02-0749 IONIZER/CELL FEED THRU INSULATOR ASSEMBLIES 37-0026 INSULATOR ONLY...
6. Note directional arrow located on the blower housing. pulley set may be required to reduce the blower rpm and amperage. The blower can be supplied either by Parker or by others. A blower WARNING curve can be requested through the blower manufacturer with the serial number.
Check operation of each amber light by placing the power pack Improper blower speeds adversely affect system toggle switch in the off position, one at time, amber light should performance. Contact Parker before adjusting motor be flashing corresponding to module identification on remote variable pulley settings.
During normal operation, with unicells in place, the component door (10) and the power pack door closed (3), the push rod (5) is in contact with unicell endplate (6). Push rod extension (1) is in contact with the ground bar (2) and bends to contact the limit switch (4).
4.1.13 Parker On Site Start Up condition of the contact spring (distorted? bent? missing?) cell The PSG system may include on site start up by a Parker contact screw (missing?), cell plates (bent? warped?) should be Field Service Technician. Usually this is listed on the order parallel and straight, repair or replace.
The “Detergent Frequency Selection” can be increased up to everyday. The auto wash cycle is initiated by a Parker time clock, with the wash cycle sequencing, wash cycle times, and detergent frequency through the unit’s PLC. A...
6.6 Rinse Procedure Cleaned components should be rinsed off quickly and thoroughly 8. Appearance Of Components to remove remaining contaminants. If the components appear After Cleaning to be clean, some detergent residue may remain. This should be removed because the residue may contribute to voltage Components should have a clean, not necessarily “new,”...
3. Leakage from some other source. Unicell components should be removed and replaced with great care to preserve gasket Figure 14 integrity. Should damaged gasket require replacement, Ionizer Wire Installation contact Parker for the correct gasket material, BUNA-N (42- 0168) or EPDM (42-1503). Parker INLET PLENUM MODULE ODOR...
9.5 Power Pack Enclosure Push Rod Adjustment Tools required: • 6” adjustable or 5/16” open-end Wrench. Refer to Figure 9. 1. Close module door (10) with unicells installed. 2. Open power pack enclosure lid cover (3). 3. Loosen 5/16” hex jam nut (9), then back off push rod extension (1) to end of threads.
If the indicator light(s) are illuminated and the unit is moving air but efficiency is below normal (unicells not dirty, • *One power pack (Parker Part Number 21-1216) smoke discharging from the exhaust blower) check for properly •...
10.4 STEP 1 — Checking the Power Pack Verify the interlock switch operation (120 VAC) to the power pack enclosure (measure voltage to the primary side of the interlock Indicator light is flashing or not illuminated switch and engage interlock switch before measuring voltage to The toggle switch should be placed in the off position to the secondary side.
(replace insulator) • Warped cell plate (s) which could be due to high duct operating temperature, consult Parker. • Ionizer wires not “taut” contacting the ground plates. • Carbon tracking to the cell high voltage feed through insulator and •...
• Unicell is structurally weak, loose steel rivets, deterioration 10.7 Bench Test Procedure to cell plate spacers or paper thin cell plates due to utilizing the improper detergent. CAUTION Parts should be replaced as required. Sometimes a flashing indicator light will clear itself by removing RISK OF ELECTRICAL SHOCK.
Page 28
Refer to “Ionizer Conditions Causing Failure” in Section 10.5. Ionizer may not be within high voltage specifications, even though manually cleaned, due to the service “age” of the unicell. The unicell should be replaced. Parts or unicell should be replaced as required. Testing Collector Cell 1.
Power pack enclosure(s) push rod Refer to Section 9.5. assembly is not properly adjusted. Fuses have failed to the power pack Replace fuses. circuit. Air volume (ACFM) is not within Measure air volume, call Parker Customer specifications. Service for specifications.
11.3 Freight Cost Freight cost on returned parts must be prepaid by the sender. Freight cost on parts shipped from Parker is prepaid by Parker and added to the cost of the parts.
12.1 Power Pack Enclosure Assembly Parts List ITEM NO. PART NO. DESCRIPTION QUANTITY REQUIRED 20-1396 Power Pack Enclosure 21-1216 Power Pack 02-1651 Shorting Out Assembly 42-10063-0001 Gasket For Lid Cover 20-2835 Terminal Block 10-11034-0002 Terminal Bracket 41-2435-5 Terminal Label 30-0121 Screw RD HD ½”...
FDNY COA #5585 CONDITIONS of APPROVAL 1. Prior to installation of the PSG electrostatic air cleaner, plans must be filed with and accepted by New York City Department of Building (DOB). Additionally, a copy of DOB docketed plans shall be transmitted to the Fire Department for review and approval. 2....
MCB, PNP, SDC, SFC, and SHM series will be free from defects in materials and workmanship for ten (10) years from the date of shipment from Parker. Subject to the terms and conditions hereof, warrants to the original...
Page 35
On claims that require repaired parts return, the claim will be processed after the part has been evaluated by the Parker IGFG Quality Department for verification of failure mode. The claims will be paid in the form of a credit to the customer’s account.
Need help?
Do you have a question about the SMOG-HOG PSG and is the answer not in the manual?
Questions and answers