Page 1
SUSPENDED WARM AIR HEATERS EOLO B modulating pre-mixed versions AE and AC...
Page 2
SYSTEMA S.p.A. EOLO BLULINE IMPORTANT!! Read carefully this manual before starting up the system. In order to improve the product, Systema reserves the right to modify the contents without any notice. SYSTEMA S.p.A. Via Antonio Ceccon, 3 Loreggia C.A.P. 35010 PADOVA - ITALIA ISO 9001:2008 Tel.
It is compulsory to follow the information indicated in this manual, particularly for what concerns the secu- rity rules. Systema disclaims any liability for any direct or indirect personal or physical injury resulting from failure to follow the instructions in this manual.
Page 6
SYSTEMA S.p.A. EOLO BLULINE The generator must be checked by qualified personnel before the start up in order to verify: - that the data of the gas and electrical power networks correspond to those standard written in this ma- nual - the correct creation and functioning of the gas exhaust pipe and of the combustion air intake...
SYSTEMA S.p.A. EOLO BLULINE CONSTRUCTION FEATURES EOLO BLULINE is the new range of hanging hot air generators with high performances. The name BLULINE represents their high performances, improved in many aspects. FUEL CONSUMPTION REDUCTION The modulation of the thermal flow of the burner in manual or auto- matic, allows to provide thermal power in relation to climate conditions.
SYSTEMA S.p.A. EOLO BLULINE EXPLODED VIEW 1.7.1 Eolo BLULINE AE helicoidal version Fig 1.11 1.7.2 Eolo BLULINE AC centrifugal series Fig 1.12 Rev. 04GB1410...
Page 21
E. BL 35 AE/AC 80VIPA5011 E. BL 15-25 AC 04CNCO2702 E. BL 45 AE/AC 80VIPA5012 E. BL 35 AC 04CNCO2703 15 Pre-mix burner brand "SYSTEMA" E. BL 55 AE/AC 80VIPA5013 E. BL 45 AC 04CNCO2700 E. BL 65 AE/AC 80VIPA5014 7b Fans hood E.
SYSTEMA S.p.A. EOLO BLULINE ELECTRICAL PLANT The electrical plant must be realized according to MAIN ELECTRONIC BOARD the national and local laws. SCP674V010 GENERAL CHA- The electrical plant must be adapted to the maxi- RACTERISTICS mum power absorbed by the equipment indicated Electrical supply: .....230 Vac +/- 10%...
SYSTEMA S.p.A. EOLO BLULINE To reset the operation, delete the alarm condition: AUXILIARY CONTROL FAN 2.1.3 a) By performing a proper maintenance to fix it. AUXILIARY CONTROL FOR THE SUMMER VEN- (This is to ensure the closure of the contact J7C).
Burner off ELECTRICAL DIAGRAM 230 VAC MONOPHASE EOLO BLULINE AE-AC ATTENTION!! EOLO WORKS WITH CONTROL PANELS SUPPLIED BY SYSTEMA. The manufacturer declines any liability for any damage caused by improper installation or improper use and / or misuse of the equipment, or from an installation with board not supplied by Systema.
SYSTEMA S.p.A. EOLO BLULINE CONNECTION DIAGRAM OF COMBUSTION UNIT AND THE INET NETWORK CONTROL BOARD FOR A SINGLE UNIT LEGEND INET CONNECTIONS (all models) Power supply (230VAC 50/60Hz) Alarm relay 3(1) A 230Vac (only for preset mod- els) C-OP External probe (only for preset models)
SYSTEMA S.p.A. EOLO BLULINE CONNECTION DIAGRAM OF THE ELECTRIC CONTROL BOARD OF INET NET- WORK WITH THE ZONE PROBES FOR ONE OR MORE COMBUSTION GROUPS LEGEND PROBES CONNECTIONS Fig 2.3 P1-P2-P3-P4 INET from 1 to 16 units - 1 Thermal zone...
External probe (only for preset models) +A, -B, S BUS INET Network connections ATTENTION: EOLO WORK EXCLUSIVELY WITH ELECTRICAL PANELS SUPPLIED BY SYSTEMA S.P.A.; the manufacturer declines all the responsibility in case of any damage caused by an 3 4 P1...
SYSTEMA S.p.A. EOLO BLULINE 2.7.1 Configuration of the board inside the machine SCP674V010 for functioning with se- veral combustion units and the INET control board Using the switch SW2 it is possible to assign an address to each network interface. The network control recognize the remote units by the number with which they have been codified, therefore it is necessary to avoid to give the same number to two different remote units, in order to exclude conflict situations with the consequent shutdown of the heating installation.
SYSTEMA S.p.A. EOLO BLULINE CONNECTION DIAGRAM COMBUSTION UNITS AND CE ON/OF CONTROL BOARD code 04CEQU1204 Control board with thermostat, reset, ON/OFF switch to control n.01 combustion unit DISPL BLOWER Configurationcontrol board SCP674V010 LED_FA LED_BLK JP1 and JP2 = CLOSED on A LED_TA SCP674V010 (REV.01)
SYSTEMA S.p.A. EOLO BLULINE CONNECTION DIAGRAM COMBUSTION UNITS AND CE ON/OFF CONTROL BOARD code 04CEQU1202 and 04CEQU1203 Control board with thermostat, reset, ON/OFF switch to control n.01 combustion unit DISPL Configurationcontrol board SCP674V010 BLOWER JP1 and JP2 = CLOSED on A...
SYSTEMA S.p.A. EOLO BLULINE GAS PIPES EQUIPMENT CONNECTION Gas supply pipes have to be realized in compliance with national and local rules. The dimensioning of the tubes and of the eventual pressure reducers/gears has to be such as to ensure the correct working of the equipments. The materials used must comply with the existing national and local laws.
SYSTEMA S.p.A. EOLO BLULINE INSTALLATION In order to reach the maximum performance of the han- ging hot air generators “EOLO” we suggest you to re- spect the following rules/laws: - Define the installation considering the type of work, the priorities zones to be heated and the absorption walls (windows, doors, gates etc.) see fig.
SYSTEMA S.p.A. EOLO BLULINE WALL INSTALLATION EXAMPLES It is possible to fix Eolo BLULINE on the building’s wall using one of the solutions shown on the following figures.. Fig.4.6 Example of wall fixing with universal brackets ATTENTION!! IN ORDER TO INSTALL A HANGING EOLO, PLEASE SPECIFY THIS CONFIGURATION WHEN YOU ORDER THE DEVICE.
SYSTEMA S.p.A. EOLO BLULINE EXAMPLES OF INSTALLATIONS OF EOLO AT A WALL WITH RORATING BRACKET (OPTIONAL) It is possible to fix to the wall of the building the generator Eolo BLULINE (ONLT THE MODELS 15 - 25 - 35 - 45 - 55 AE) using one of the solutions illustrated in the following figures.
SYSTEMA S.p.A. EOLO BLULINE CENTRIFUGAL INSTALLATION EXAMPLE On the following figure it is described an example of installation of a centrifugal Eolo, installed inside and canalized. The air intake is from outside and from inside with possibility to regulate the internal/external air mixture.
SYSTEMA S.p.A. EOLO BLULINE EXHAUST AND SUCTION DUCTS Type C53 Type B23 Type B23 Maximum pipe length Maximum pipe length Maximum pipe length 6+6 meters Ø100 mm 8 meters Ø100 mm 8 meters Ø100 mm Type C33 Type C33 Type C13...
SYSTEMA S.p.A. EOLO BLULINE SEPARATE WALL DISCHARGE TYPE C13 Pos. Description Code Q.ty 1 Wall fumes terminals Ø100 mm with hole cover rosette 04CNTE0445 2 Wall air terminals Ø 100 mm with hole cover rosette 04CNTE0446 3 Stainless steel joint flexible/rigid pipe F Ø 100 mm 00CNGI2542 4 Stainless steel flexible air pipe Ø...
SYSTEMA S.p.A. EOLO BLULINE TESTING AND EQUIPMENT START UP PRELIMINARY OPERATIONS Before starting Eolo BLULINE, we suggest to check the following: 1) Control the correct electrical connection between burner, control panel and the electrical supply net. 2) Verify that the equipment are provided for the type of gas available (eventually refer to paragraph 6.5 on fuel change), verify the net pressure (see tab 6.4 on page 48) and open gas: verify that the gas flow...
SYSTEMA S.p.A. EOLO BLULINE 6.3.1 Regulations on generators with 848 Sigma valve 1) Place the manometer on point (6) of the gas valve for the detection of the gas outlet pressure. 2) Use the fumes analyzer to verify if the combustion values are cor- rect and if they correspond in paragraphs 8.
SYSTEMA S.p.A. EOLO BLULINE 6.3.2 Regulations on generators with 822 Nova Mix valve 1) place the manometer on point (2) of the gas valve to detect the ou- tlet gas pressure. 2) use the fumes analyzer to verify that combustion values are correct and correspond in paragraphs 8.
SYSTEMA S.p.A. EOLO BLULINE 6.3.3 Air mixer The air-gas mixer placed upstream the burner fan, provide the burner with the right air and gas volume. The air re- gulation mustn’t be modified except of constructor indication. Pos. Description Air/gas mixer Gas inlet...
SYSTEMA S.p.A. EOLO BLULINE FUEL CHANGE The gas/nozzle change must be performed by technical qualified personnel in compliance with the security laws and with this manual. The constructor disclaims any responsibility in case of damages deriving from wrong transforma- tion or improper and/or incorrect appliance use.
ATTENTION PWM VALUES, WHICH HAVE BEEN SET BY THE CONSTRUCTOR, CANNOT BE CHANGED. They can be modified only by company Systema's specialized personnel. EOLO BL 15 EOLO BL 25 EOLO BL 35...
WARRANTY COVER AND VALIDITY 1) The warranty is limited to the faults of the heater components supplied by SYSTEMA. In the event of a fault of components or in case of production defect, SYSTEMA shall repair or replace faulty parts ex- works free of charge.
SYSTEMA S.p.A. EOLO BLULINE SETTING ASIDE ATTENTION! All disconnection operations must be preformed by authorized technical personnel! If the appliance is to be set aside for a lengthy period of time, the following operations must be performed: Turn the main switch to “0” and disconnect the appliance from the power supply.
Page 52
To continually improve the products, SYSTEMA S.p.A. reserves the right to alter the characteristics with- out prior notice.