Manual1: Backup operation in the presence of power, through manual activation and signal from external logic
At least one of the following STOP conditions must be met for the backup mode output:
1. Press 'ESC' on the display for at least 5 seconds
INPUT
CONDITION
2. External control signal cancelled (open contact)
S
Once it has left the backup mode, the inverter will check the conditions of the network and, after ensuring
that Voltage and Frequency parameters are correct, it will start the reconnection sequence.
Manual1: External logic linked to power failure, backup operation through manual activation
Application Note| REACT-3.6/4.6-TL – BACKUP OUTPUT|Operation and Configuration 8