Watts AERCO Benchmark Platinum 750 Reference Manual page 86

Boilers with edge [ii] controller
Table of Contents

Advertisement

Benchmark Platinum with Edge [II]: Reference Manual
SECTION 6: BENCHMARK PLATINUM 5000 & 6000 PART LIST
Benchmark Platinum 5000-6000 Valve Proving System (VPS)
P/N 24655 rev B, 5/4/2018
Item Qty Part #
1
1
24629-5
2
1
33261
RED ALARM LIGHT & RESET SWITCH
1. OFF during normal operation
2. ON indicates a leak or Actuator
failure
The Benchmark gas train P/N 22308-4 operates in conjunction with a Valve Proving System.
This system monitors the gas pressure on both sides of the Actuator. If the pressure difference
falls below a fixed value, indicating the failure of the Actuator or leakage in the gas line, it
triggers the shutdown of the boiler.
Once the problem has been diagnosed and corrected, the Valve Proving System must be reset
by pressing the red Reset switch before the unit is restarted.
OMM-0138_D • GF-212 • 2/24/2021
Description
VALVE PROVING SYSTEM ASSEMBLY
BRACKET, VPS SUPPORT
YELLOW RUN LIGHT
1. OFF during normal operation
2. ON during valve proving operation
3. ON when unit is not running
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Item Qty Part #
Description
6
1
97087-48
FLEXIBLE GAS TUBE (NOT SHOWN)
7
1
97087-26
FLEXIBLE GAS TUBE (NOT SHOWN)
1
2