Watts AERCO Benchmark Platinum 750 Reference Manual page 61

Boilers with edge [ii] controller
Table of Contents

Advertisement

Benchmark Platinum with Edge [II]: Reference Manual
SECTION 5: BENCHMARK PLATINUM 4000-5000N PART LIST
Valve Proving System (VPS)
One Benchmark 4000 gas train (22373-4) and one 5000N and gas train (22358-4) include the Valve
Proving System. This devise monitors the gas pressure on both sides of the Actuator. If the
pressure difference falls below a fixed value, indicating the failure of the Actuator or leakage in the
gas line, it triggers the shutdown of the unit. When this occurs, a SSOV SWITCH OPEN message
appears in the Edge Controller display.
Once the problem has been diagnosed and corrected, the Valve Proving device must be reset. This
is done by pressing the red RESET switch before the unit is restarted; the Edge Controller must
also be reset.
RED ALARM LIGHT & RESET SWITCH
OFF during normal operation
ON indicates a leak or Actuator failure
OMM-0138_D • GF-212 • 2/24/2021
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
YELLOW RUN LIGHT
OFF during normal operation
ON during valve proving operation
ON when the unit is in standby
Page 61 of 91

Advertisement

Table of Contents
loading

Table of Contents