AP PAR ATU S CO NTR O L T E S TI NG
Step 5/10
On the protection relay LHMI (upstream circuit breaker) go to -> Main Menu/Monitoring/
I/O status/Current protection/PHIPTOC1/Inputs
– BLOCK = True
Figure 83: Activating blocking mode
Step 6/10
On the protection relay LHMI (tested feeder) go to-> Main Menu/Test/Function tests/
Current protection
– PHIPTOC1 = Deactivate START
Figure 84: Deactivating START signal
1 VLG 500 0 17 C
I NT ER LO C K S BE T W EE N PA NE LS
55