Huawei FusionServer Pro XH628 V5 Server Node
Technical White Paper
Category
Relative humidity (RH,
non-condensing)
Altitude
Corrosive gaseous
contaminant
Particle contaminant

6.3 Physical Specifications

Table 6-3 Physical specifications
Category
Dimensions (H x W x
D)
Weight in full
configuration
Issue 05 (2020-09-03)
Specifications
● Operating humidity: 5% to 85%
● Storage humidity (≤ 72 hours): 5% to 95%
● Long-term storage humidity (> 72 hours): 30% to
69%
● Maximum change rate: 20%/h
● Operating altitude ≤ 3050 m (10006.44 ft)
– If the server complies with ASHRAE Class A2, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 300 m (984.25
ft) in altitude above 900 m (2952.76 ft).
– If the server complies with ASHRAE Class A3, the
maximum operating temperature decreases by
1°C (1.8°F) for every increase of 175 m (574.15
ft) in altitude above 900 m (2952.76 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
● Titanium PSUs are required for the altitude higher
than 3050 m (10006.44 ft).
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the
equipment room be monitored by a professional agency.
Specifications
166 mm x 109 mm x 745 mm (6.54 in. x 4.29 in. x
29.33 in.)
● Net weight: 20 kg (44.1 lb)
● Packaging materials: 4.35 kg (9.59 lb)
Copyright © Huawei Technologies Co., Ltd.
6 Product Specifications
42