User Select - nilan CTS 602 User Manual

Vpm 120; vpm 240; vpm 480; vpm 560;
Hide thumbs Also See for CTS 602:
Table of Contents

Advertisement

User select

The menu CUSTOM OPTIONS overrides the operating mode of the main menu by activating an
external switch.
There are four custom options: "exhaust" and "inlet", "extend" and "OFF"
"VENTILAT": There is a possibility here to run with a higher or lower speed on the air exhaust and
air inlet for a limited amount of time. The external pressure will activate the function. The function
has high priority.
"EXHAUST" and "INLET": These two options increase or reduce the velocity of the exhaust or inlet
air respectively for a limited period of time. The remaining functions of the operating mode remain
unaltered. An external switch activates the timer function.
Another external switch ensures that the fans remain at the desired ventilation level until the switch
is turned off.
"EXTEND": This option controls the velocity of the exhaust and inlet air and can be used to change
the temperature of the inlet air for a limited period of time. An external switch activates the timer
function.
"OFF": Deactivates the external switch.
Options that flash are indicated by " ".
ENTER
USER
SELECT
Required period in
which the selected
function is to remain
operative: stated in
hours and minutes.
Max 8 hours.
Required ventilation
step: 1-4.
OFF allows the system
to be shut down via an
external switch.
May be subject to change
On the CTS 602 control panel, press:
- ESC to return to the previous menu
- qp to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a new menu option setting
- OFF to switch off the controls
- ON to switch on the controls
SELECT
ENTER
"EXTEND"
TIME
TIME
ENTER
00:00
FLOW
FLOW
ENTER
>4<
TEMP
TEMP
ENTER
23
°C
Required room temperature
(5-30°C).
T15 is the temperature sensor to
be used to control the system.
Figure 9: The "User select" menu
SELECT
"VENTILAT"
SELECT
"EXHAUST"
SELECT
"00:00"
"INLET"
SELECT
">4<"
"EXTEND"
SELECT
"OFF"
"23" °C
ENTER
Possibility to run at
a higher or lower
rate. High priority.
ENTER
ENTER
Time and speed must
be set in the same
way as described
under SELECT
EXTEND.
ENTER
Switches user option
off.
page 14 af 28