Initial commissioning

The control unit performs the following additional functions automatically:
Checking the battery voltage
The control unit checks the battery voltage 2x daily and signals a battery error (potential-free contact "fault") if the voltage
falls below a certain level. Optical and acoustic warning signals appear on the control unit every 20 seconds.
SDS self-check
The control unit has an automatic self-check, which performs a functional check of the connected movable components
automatically. Even if the pumpt does not operate, the system's readiness is checked.
Preset test cycle:
every 28 days (1-28 day interval is possible)
5.1
Switch on and off
Connect the battery
Connect the battery connector(s) (2).
Establish mains voltage (400V control units)
Connect the mains cable to the mains power supply.
Move main switch (1) into ON position.
Initialisation starts automatically.
The device checks the electrical components.
Voltage test of the standby batteries.
|3.10. Languagee|
Menu item
Switch on
Move main switch (1) into ON position. After a successful
system test, the display shows
the green LED signals readiness.
If the display does not show initialisation (
guage|
) the control unit has already been initialised. In
this case, the set parameters must be checked, or reset to
|3.11 Reset|
the factory settings (
the factory settings, the initialisation of the control unit starts
automatically.
Please note that the counter for the maintenance interval is
not changed by the reset to the factory settings.
Activating operating mode
Press OK button on the control panel, background lighting of the display lights up and the
displayed.
34 / 140
is displayed.
|0 System info|
and
|3.10. Lan-
). After resetting to
Installation and operating instructions
|0 System info|
menu is
010-990