Red Ion CUB5 Manual page 12

Miniature electronic 8-digit dual counter and rate indicator
Table of Contents

Advertisement

SETPOINT OUTPUT TIME-OUT
SPn tOUt
0. 0 1
001. 0 0
This parameter is only active if the Setpoint Action is set to time out (
Enter the value in seconds that the Setpoint output will be active, once the
Setpoint Value is reached.
SETPOINT VALUE
SPn VAL
Count A:
Count B:
00000100
Enter the desired Setpoint value. To enter a negative setpoint value,
increment digit 8 to display a "-" sign (Counter A only).
SETPOINT OUTPUT LOGIC
SPn OUt
NOr
Normal (
) turns the output "on" when activated and "off" when
NOr
deactivated. Reverse (
) turns the output "off" when activated and "on" when
rEV
deactivated.
SETPOINT ANNUNCIATOR
SPn LIt
NOr
Normal (
) displays the setpoint annunciator when the corresponding
NOr
output is "on". Reverse (
) displays the setpoint annunciator when the output
rEV
is "off".
SETPOINT OUTPUT POWER-UP STATE
SPn P-UP
OFF
will restore the output to the same state it was at before the meter was
SAVE
powered down.
will activate the output at power up.
ON
output at power up.
SETPOINT BOUNDARY TYPE
SPn tYPE
HI-ACt
HI-ACt
High Acting Boundary Type activates the output when the assigned display
value (
) equals or exceeds the Setpoint value. Low Acting activates the
SPn ASN
output when the assigned display value is less than or equal to the Setpoint.
SETPOINT STANDBY OPERATION
SPn StbY
NO
NO
This parameter only applies to Low Acting Boundary Type setpoints. Select
to disable a Low Acting Setpoint at power-up, until the assigned display
YES
value crosses into the output "off" area. Once in the output "off" area, the
Setpoint will then function per the description for Low Acting Boundary Type.
to
599. 9 9
seconds
9999999
to
99999999
-
0
to
9999999
Rate:
0
to
999999
NOr
rEV
NOr
rEV
OFF
ON
SAVE
will deactivate the
OFF
LO-ACt
YES
SPn AUtO
NO
).
t-OUt
This parameter automatically resets the counter to which the setpoint is
assigned (
) each time the setpoint value is reached. The automatic reset
SPn ASN
can occur at output start, or at output end if the Setpoint Output Action is
programmed for timed output mode. The Reset-to-Count Load selections
("
") only apply to Counter A assignment. This reset may be different from
CtLd-
the Counter A Reset Action selected in Module 1.
SELECTION
ACTION
No Auto Reset.
NO
2Ero-Str
Reset to Zero at the start of output activation.
Reset to Count Load value at the start of output activation.
CtLd-Str
Reset to Zero at the end of output activation (timed out only).
2Ero-End
Reset to Count Load value at the end of output activation
CtLd-End
(timed out only).
SETPOINT 1 OUTPUT OFF AT SETPOINT 2 (SP1 Only)
SP1 OFF2
NO
This parameter will deactivate Setpoint 1 output at the Start or End of
Setpoint 2 output (O1 off at O2). The "
Output Action is programmed for timed output.
SETPOINT 2 OUTPUT OFF AT SETPOINT 1 (SP2 Only)
SP2 OFF1
NO
This parameter will deactivate Setpoint 2 output at the Start or End of
Setpoint 1 output (O2 off at O1). The "
Output Action is programmed for timed output.
SETPOINT OUTPUT RESET WITH MANUAL RESET
SPn rSt
YES
Selecting
causes the Setpoint output to deactivate (reset) when the
YES
Setpoint Assigned Counter is reset. The counter reset can occur by the
button, User Input, Counter Reset at Power-up or a serial Reset Counter
command.
This output reset will not occur when the Assigned Counter is reset by a
Setpoint generated Counter Auto Reset.
CHANGE DISPLAY COLOR WITH OUTPUT STATE
SPn ChC
NO
This parameter enables the backlight CUB5 to switch the backlight color when
the output state changes. This parameter is only active for the backlight version.
12
COUNTER AUTO RESET
NO
@2Ero-Str
2Ero-End
NO
Out2-Str
Out2-End
" setting only applies if Setpoint 2
-End
NO
Out1-Str
Out1-End
" setting only applies if Setpoint 1
-End
YES
NO
NO
YES
CtLd-Str
CtLd-End
RST