Carrier AquaEdge 19DV Controls Operation And Troubleshooting page 86

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic6 controls
Table of Contents

Advertisement

OBJECT NAME
HYDRLIC_cdw_pd
HYDRLIC_CDWP
HYDRLIC_CHW_FLOW
HYDRLIC_CHW_FV
HYDRLIC_chw_pd
HYDRLIC_CHWP
HYDRLIC_ctrlw_dt
INPUTS_bacdongl
INPUTS_DIFF_ACT
INPUTS_DMP_ACT
Cl=0,Inter=1,Op=2,Fail=3
INPUTS_E_STOP
INPUTS_FS_LOCK
INPUTS_GV1_ACT
INPUTS_GV2_ACT
INPUTS_HF_LS
INPUTS_HGBP_ACT
Cl=0,Inter=1,Op=2,Fail=3
INPUTS_HGBPACTP
INPUTS_HP_SW
INPUTS_ICE_CON
INPUTS_PGLE_HI
INPUTS_PGLE_LO
INPUTS_REM_CON
INPUTS_REM_LOCK
INPUTS_SAFETY
INPUTS_STAR_AUX
INPUTS_STARTFLT
INPUTS_TRIPR
INPUTS_VFD_ACT
LABONLY_gv1_fc
LABONLY_gv2_fc
MAIN_MS_lag_s_s
MAIN_MS_lagstart
MAIN_MS_lagstat
MAIN_MS_lagstop
MAIN_MS_lead_lag
Disable=0, Lead=1, Lag=2
MAIN_MS_ll_comm
MAIN_MS_ll_fault
No Fault=0, Master=1
Slave=2, Both=3
MAIN_MS_ll_hr_d
MAIN_MS_ms_ctrl
MAIN_MS_preflt
MAIN_MS_pulltime
MAIN_MS_sl_ctrl
Local=0, Network=1
Remote=2, Local Sched=3
MAIN_SRD_diff_alm
MAIN_SRD_diff_tgt
MAIN_SRD_diffault
MAIN_SRD_lift_1
MAIN_SRD_lift_2
MAIN_SRD_lift_a
MAISURGE_act_reg
No=0, Low=1, High=2
Deadband=3, Noise=4
MAISURGE_dts_act
MAISURGE_dts_cal
MAISURGE_dts_maxc
MAISURGE_dts_medc
MAISURGE_dts_minc
MAISURGE_enlp_opt
MAISURGE_gv1_sful
MAISURGE_gv1_smed
MAISURGE_gv1_smin
MAISURGE_sc
MAISURGE_spc
MAISURGE_surg_act
MAISURGE_surg_pro
APPENDIX D — NETWORK CONFIGURATION (CONT)
OBJECT TYPE
INSTANCE
AV
59
BV
49
BV
52
AV
60
AV
61
BV
51
AV
62
BV
20
AV
47
MV
BV
13
BV
18
AV
44
AV
45
BV
23
MV
AV
48
BV
11
BV
14
BV
22
BV
21
BV
12
BV
15
BV
16
BV
10
BV
17
BV
19
AV
46
BV
61
BV
62
BV
60
AV
121
AV
120
AV
122
AV
116
BV
59
AV
119
AV
125
AV
117
AV
123
AV
124
AV
118
BV
58
AV
112
BV
57
AV
114
AV
115
AV
113
AV
96
AV
97
AV
98
AV
103
AV
105
AV
104
AV
109
AV
106
AV
108
AV
107
AV
99
AV
100
AV
101
AV
102
OPTION
PV ACCESS
2
3
86
DESCRIPTION
RO
Condenser Water Delta P
RO
Condenser Water Pump
RO
Chilled Water Flow
RO
Chilled Water Flow Value
RO
Chilled Water Delta P
RO
Chilled Water Pump
RO
Controlled Water DT
RO
BACnet Dongle
RO
Diffuser Actual Pos
RO
Damper Valve Status
RO
Emergency Stop Contact
RO
Fire Security Interlock
RO
Guide Vane 1 Actual Pos
RO
Guide Vane 2 Actual Pos
RO
Liquid Level Switch
RO
EC Valve Status
RO
Actual ECV Pos Per
RO
High Pressure Switch
RO
Ice Build Contact
RO
Purge Level Switch High
RO
Purge Level Switch Low
RO
Remote Contact
RO
Chiller Lockout
RO
Spare Safety Input
RO
Compressor Start Contact
RO
Starter Fault Feedback
RO
ISM Trip Relay Status
RO
Actual VFD Speed Per
RO
GV1 Forced
RO
GV2 Forced
RO
Slave Start/Stop
RO
Lag Start Timer
RO
Slave Run Status
RO
Lag Stop Timer
RO
Unit is Lead or Lag
RO
Lead Lag Communication
RO
Master Slave Fault
RO
Lead/Lag Hours Delta
RO
Master Control Type
RO
Prestart Fault Timer
RO
Pulldown Timer
RO
Slave Control Type
RO
SRD Rotating Stall Alarm
RO
Diffuser Target Pos
RO
Diffuser Fault
RO
VDO High Lift Load Line
RO
VDO Low Lift Load Line
RO
Actual Lift
RO
Surge Region
RO
Actual Delta Tsat
RO
Calc Ref Delta Tsat
RO
Cal Surge Delta Tsmax
RO
Cal Surge Delta Tsmed
RO
Cal Surge Delta Tsmin
RO
Envelope Line Optimized
RO
IGV1 Full Load Position
RO
Opti-Sound IGV1 Position
RO
IGV1 Minimum Position
RO
Surge Counts
RO
Surge Protection Counts
RO
Surge Prevention Active
RO
Surge Protection Active