Carrier AquaEdge 19DV Controls Operation And Troubleshooting page 40

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic6 controls
Table of Contents

Advertisement

DESCRIPTION
ALARM CODE
OF ALARM TEXT
VFD Fault - Line
ALM-446
Voltage
Imbalance
VFD Fault -
ALM-447
Frequency Fault
VFD Fault - VFD
ALM-448
Comm Fail
VFD Fault - VFD
ALM-449
Fault
VFD Fault - VFD
ALM-450
Start Inhibit
VFD Fault - VFD
ALM-451
Checksum Error
VFD Fault -
ALM-452
Inductor
Overtemp Switch
VFD Fault -
ALM-453
Incompatibility
Fault
VFD Fault - Main
ALM-454
Power Failure
VFD Fault -
ALM-500
Brake Check
VFD Fault -
ALM-501
Power Card Over
Temperature
VFD Fault - Earth
ALM-502
Fault
VFD Fault - Ctrl
ALM-503
Card Over
Temperature
VFD Fault -
ALM-504
Control Word
Timeout
VFD Fault - Over
ALM-505
Current
VFD Fault -
ALM-506
Torque Limit
VFD Fault -
ALM-507
Motor Thermistor
Over Temp
VFD Fault -
ALM-508
Motor Etr Over
Temperature
VFD Fault -
ALM-509
Inverter Overload Manual
VFD Fault - DC
ALM-510
Link Under
Voltage
VFD Fault - DC
ALM-511
Link Over
Voltage
VFD Fault - Short
ALM-512
Circuit
VFD Fault -
ALM-513
Inrush Fault
VFD Fault -
ALM-514
Mains Phase
Loss
VFD Fault - AMA
ALM-515
Not OK
VFD Fault - Live
ALM-516
Zero Error
VFD Fault -
ALM-517
Internal Fault
VFD Fault -
ALM-518
Brake OverLoad
Table 16 — PIC6 Alarm Codes* (cont)
ACTION TAKEN BY
RESET TYPE
THE CONTROL
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on. Refer to Danfoss VFD trouble shooting manual
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Alarm relay turns on. Refer to Danfoss VFD trouble shooting manual
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on. Refer to Danfoss VFD trouble shooting manual
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on. Refer to Danfoss VFD trouble shooting manual
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on. Refer to Danfoss VFD trouble shooting manual
Unit shuts down.
Manual
Alarm relay turns on.
Unit shuts down.
Manual
Alarm relay turns on.
POSSIBLE CAUSE
Check phase-to-phase and phase-to-ground distribution bus voltage.
Increase Line Voltage Imbalance% in CFGUMVFD screen.
Check Power Supply
If operating from a generator, check generator size and speed.
Check utility power supply.
Check VFD communication wiring and connectors.
Check status lights on DPI Communications Interface Board.
Call Carrier Service.
Check fault code and possible cause in corresponding type of VFD user
manuals
Call Carrier Service
The VFD Start Inhibit is derived from the Alarm bit being set in the VFD.
The conditions causing the alarm must be corrected in the VFD to
enable subsequent starts and operation
Press Reset to Restore Configuration.
Actual VFD checksum does not match calculated value.
Check Temp Switch and Cooling Fans.
Check for cooling fan air flow obstructions
Load compatible version files into drive
Check the main power to VFD
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
Refer to Danfoss VFD trouble shooting manual
40