Carrier AquaEdge 19DV Controls Operation And Troubleshooting page 3

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic6 controls
Table of Contents

Advertisement

Table 1 — IOB Configuration
ANALOG INPUT
0
Disable
1
0 to 5 VDC
2
4 to 20 mA
3
10 k (thermistor)
4
5 k (thermistor)
5
Ohm (Shift_Dis)
6
100 Ohm RTD
DESCRIPTION
Entering Chilled Water Temperature
Leaving Chilled Water Temperature
Entering Condenser Water Temperature
Leaving Condenser Water Temperature
Evaporator Refrigerant Liquid Temperature
Discharge Gas Temperature
Condenser Pressure
Evaporator Pressure
Chiller Status Output (ON=20mA, OFF=4mA, TRIPOUT=8mA,
Not Off and Compressor not running=12mA)
Evaporator Flow Switch
Condenser Water Flow Switch
Remote Contact
Remote Emergency Stop Input
Economizer Bypass Valve
Refrigerant Pump
Chiller Alarm Relay
Vapor Venting Line SV (Free cooling option)
LEGEND
IOB — Input/Output Board
NO — Normally Open
SV
— Solenoid Valve
NOTES:
DESCRIPTION
Motor Winding Temperature 1
EC/HGBP Valve Feedback
Pump Output Pressure
Bearing Outlet Pressure
Bearing Inlet Pressure
Auto Demand Limit Input
Refrigerant Leak Sensor
Pump Input Pressure
Guide Vane 1 Output
EC/HGBP Modulating Output
Liquid Level Switch
High Pressure Switch
Ice Build Contact
Condenser Control Valve
Evaporator Control Valve
Economizer Isolation Valve (Liquid Bypass Option)
LEGEND
EC
— Envelope Control
HGBP — Hot Gas Bypass
IOB
— Input/Output Board
NO
— Normally Open
ANALOG OUTPUT
0
Disable
1
4 to 20 mA
2
0 to 10 VDC
Table 2 — 19DV IOB1 Connections
CHANNEL
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
AO1
DI1
DI2
DI3
DI4
DO1
DO2
DO3
DO4
Table 3 — 19DV IOB2 Connections
CHANNEL
AI1
AI3
AI5
AI6
AI7
AI8
AI9
AI10
AO1
AO3
DI2
DI3
DI4
DO1
DO2
DO4
3
19DV IOB COMPONENTS AND WIRING
The components listed in Tables 2-5 are available at the user's
terminal block on the IOB. Some are available only if the unit
is operating in Remote mode. Table 6 lists SIOB inputs and out-
puts. Figures 2-4 show IOB wiring diagrams and Fig. 5 is the
legend. Figures 6-9 show additional control wiring.
TERMINAL
TYPE
J16-1,5
5 k
J16-2,6
5 k
J16-3,7
5 k
J16-4,8
5 k
J15-6,12
5 k
J15-5,11
5 k
J15-4,10
5 VDC
J15-3,9
5 VDC
J14-1,4
4 to 20 mA
J13-5 (5TB-9,10)
24 VAC
J13-6 (5TB-11,12)
24 VAC
J13-7 (5TB-13,14)
24 VAC
J13-8 (5TB-15, 16)
24 VAC
J12-7
24 VAC
J12-10
24 VAC
J12-2 (5TB-3,4)
24 VAC
J12-5
24 VAC
1.
See Fig. 2 for IOB1 wiring diagram.
2.
For pressure readings, only Vout (output) terminal is indicated. See Fig. 2 for
Vin (+) and ground (–).
3.
Defaults are shown. In some cases the IOB can be configured differently
depending on job requirements.
TERMINAL
TYPE
J16-1,5
5 k
J16-3,7
4 to 20 mA
J15-6,12
5 VDC
J15-5,11
5 VDC
J15-4,10
5 VDC
J15-3,9 (5TB-23,24)
4 to 20 mA
J15-2,8 (5TB,25,26)
4 to 20 mA
J15-1,7
5 VDC
J14-1,4
4 to 20 mA
J14-3,6
4 to 20 mA
J13-6
24 VAC
J13-7
24 VAC
J13-8,4, (5TB-17,18)
24 VAC
J12-7
24 VAC
J12-10
24 VAC
J12-5
24 VAC
NOTES:
1.
See Fig. 3 for IOB2 wiring diagram.
2.
For pressure readings, only Vout (output) terminal is indicated. See Fig. 3 for
Vin (+) and ground (–).
3.
Defaults are shown. In some cases the IOB can be configured differently
depending on job requirements.
OPTIONAL
Yes
Yes, NO (dry contact)
Yes, NO (dry contact)
Yes, NO (dry contact);
closed indicates start chiller signal
Yes, NO (dry contact);
closed indicates stop chiller signal
Yes
Yes
Yes
OPTIONAL
Yes
Yes
Yes
Yes
Yes, NO (dry contact)