Diagnostics; Simulation; Error Codes - Vega VEGAPULS 51K Operating Instructions Manual

Table of Contents

Advertisement

6 Diagnostics

6.1 Simulation

To simulate a certain filling level, you can call
up the function "Simulation" in the adjustment
module MINICOM, in the adjustment software
PACT ware
TM
or in the HART
You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC,
react according to their adjustments and will
probably activate alarms or system func-
tions. One hour after the last simulation ad-
justment, the sensor returns automatically to
standard operating mode.

6.2 Error codes

Display
Meaning
E013
No valid measured value
- Sensor in the warm-up
phase
- Loss of the useful echo
E017
Adjustment span too small
E036
Sensor software does not
run
E040
Hardware failure/Electronics Check all connection cables.
defective
50
®
handheld.
Message is displayed during warm-up phase
If the message remains, a false echo storage
must be carried out with the adjustment module
MINICOM in the menu "sensor optimisation" or
better, with the PC and VVO.
If the message still remains, carry out a new
adjustment.
Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm.
- Sensor must be programmed with new
- Message appears during a software update.
Contact our service department.
Rectifying measure
software (service)
Diagnostics
VEGAPULS 51K ... 54K