Huawei FusionServer Pro 2488H V6 Technical White Paper page 83

Table of Contents

Advertisement

Huawei FusionServer Pro 2488H V6 Server
Technical White Paper
Category
Relative humidity (RH,
non-condensing)
Air volume
Operating altitude
Corrosive gaseous
contaminant
Particle contaminant
Issue 03 (2021-02-01)
Specifications
● Operating humidity: 8% to 90%
● Storage humidity (≤ 72 hours): 5% to 95%
● Storage humidity (> 72 hours): 30% to 69%
● Maximum humidity change rate: 20%/h
≥ 196 cubic feet per minute (CFM)
≤ 3050 m (10006.44 ft)
● When the server configuration complies with
ASHRAE Classes A1 and A2 and the altitude is above
900 m (2952.76 ft), the highest operating
temperature decreases by 1°C (1.8°F) for every
increase of 300 m (984.24 ft).
● When the server configuration complies with
ASHRAE Class A3 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 175 m
(574.14 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollutants in the
equipment room be monitored by a professional organization.
Copyright © Huawei Technologies Co., Ltd.
6 Product Specifications
76