To change the set point and the variables set in factory:
-
Press any of the 4 keys on the front panel.
-
The words "Set Point" appear on the display. Use the keys
(factory setting: 150Pa)
S1: 60
Set Point: 150
-
Press the key
the bottom of the pressure sensor scale. Use the keys
setting: 0 – 300Pa)
S1: 60
Range: 0-50
-
Press the key
of motor response by means of changes in network pressure It is advisable to not
change the settings. Use the keys
S1: 60
Kp: 1000
-
Press the key
of motor response by means of changes in network pressure It is advisable to not
change the settings. Use the keys
S1: 60
Ki: 100
"PROPORTIONAL" mode
In this mode, the CONTROL ECOWATT is set up to work with one, two or three analogical
inputs (J6, J7 or J8), 4-20mA or 0-10V. The CONTROL ECOWATT functions in accordance
with the parameter of maximum demand. The sensors are connected in the inputs S1(J6),
S2(J7) and S3(J8). Depending on the type of sensor (4-20mA or 0-10V) set the micro switch
fitted in the circuit board to "mA" or "V".
Output
MAX output
Speed
range
MIN output
16
PR-OUT: 80%
p
to move to the next parameter: "Range". This parameter allows entry to
PR-OUT: 80%
p
to move to the next parameter: "Kp". This parameter allows modification
-
PR-OUT: 80%
p
to move to the next parameter: "Ki". This parameter allows modification
-
PR-OUT: 80%
Useful sensor range
(IN (+/-))
IN
IN
P
min
-
or
+
to change setting (factory setting: 1000)
or
+
to change setting (factory setting: 100)
Input
max
-
or
+
to change setting
or
+
to change setting (factory