S&P CONTROL ECOWATT Manual page 15

Hide thumbs Also See for CONTROL ECOWATT:

Advertisement

Available languages

Available languages

PR-OUT:
- % of 0-10V output for CONTROL ECOWATT AC/DC
- % of range of voltage adjustment for AC/4A CONTROL ECOWATT
P1, P2 or P3:
Settings at the average point of the selected range of functioning adjusted to the premises
where the sensor is installed..
Four adjustment keys:
-
and
keys for changing the menus
-
-
and
+
keys for changing the settings
LED indicating input signal for sensors S1, S2 and S3
LED indicating output signal or output voltage level (according to model)
Green LED "POWER ON" that indicates that the CONTROL ECOWATT is switched on.
Red LED "ERROR" that indicates a CONTROL ECOWATT function error.
SETTINGS
All models in the CONTROL ECOWATT range have three function modes:
PI
PROPORTIONAL INTEGRAL
PROPORTIONAL
MINI MAXI
Changing the function settings
-
After switching on the CONTROL ECOWATT, press one of the four keys on the front
panel (within 10s).
-
Press the keys – o + to change function mode (factory setting: PROPORTIONAL
INTEGRAL )
"PROPORTIONAL INTEGRAL" mode
In this mode, the CONTROL ECOWATT is set up to function in a constant pressure system so a
single input value is possible, the Pascal set point value that we want to maintain in the duct
network. Only the S1 input may be used, connected to a TDP-type pressure transmitter.
S1: 150%
PR-OUT:
50%
P1: 150 Pa
Output
MAX output
Speed
range
MIN output
Input
P
15