Mns-Up Module Installation; Lifting Of Modules; Adding Of Module Sets; Removing Of Module Sets - ABB MNS-Up Service Manual

Hide thumbs Also See for MNS-Up:
Table of Contents

Advertisement

MNS-Up module installation

9.1 Lifting of modules

Wheelchair lifts are recommended for lifting modules up or down.
Model:
NEWBINGO 100 (height 2000 mm, with shelf mounted over the
forks)
Manufacturer/supplier:
LEVANTE Srl
Via dell'economia 10
46035 Ostiglia Mantova
Tel: 0039 0386801814
Web: www.levantelift.com
32

9.2 Adding of module sets

MNS-Up modules are always installed as a complete set, since
none of the modules can work independently.
To install a new module set the following steps are recommended:
 
If possible, switched OFF the complete system and
disconnected the loads.
– If no redundancy is present, the load must be
disconnected
– If redundancy N+1 is present, disconnecting the load
is not mandatory (see "hot swappable" definition) but
is recommended
 
§ Remove the active and passive module space
covers.
§ Install the passive module first.
§ Install active module.
§ Install filter module.
 
Follow the start-up procedure as described in the
DPA500 user manual section 5.15.2.2.

9.3 Removing of module sets

 
Turn down the MNS-Up module as described in the
DPA500 manual 5.15.2.1.
– Disconnect and pull the filter module to isolate the
MNS-Up module completely.
– Disconnect active module and pull to disconnected
position.
– Disconnect passive module and pull to disconnected
position.
Module stoppers for active and passive modules to
prevent dropping
09
MNS-Up Service Manual

Advertisement

Table of Contents
loading

Table of Contents