Honeywell NOTIFIER AM-8200 Installation Manual page 42

Fire detection system
Hide thumbs Also See for NOTIFIER AM-8200:
Table of Contents

Advertisement

Item
AM-8200BB
AM-8200BB
LIB-8200
AM82-2S2C
AM82-BST-C
SIB-8200
Devices connected to Sounder Output
2
Loops
2
Current
Refer to Table 3
Loop 1
Loop 2
Loop 3
Loop 4
3
User Output current
LCD-8200
Bells
Sounders
Strobes
Other devices
1 Check the load for each output is within admitted limits
2 Current from loops: Refer to the device manufacturer data sheet for the current necessary in normal mode.
Calculate the total current required for each loop by using the table 2 (refer to the following).
Alarm current: Refer to the devices manufacturer' data sheet for the current necessary in alarm mode.
Calculate the total current required for each loop by using the table 2 (refer to the following) taking into account that the control unit controls
the activation only of the first 6 sensor and input module LED in alarm
Check that the total current for each loop is lower than 750 mA.
3 Refer to the device manufacturer data sheet for the current necessary in normal and alarm mode. Check that the total current is lower than
2 Ampere.
4 The current request for the stand-by or alarm conditions cannot, in any case, exceed the power supply capacity. If the calculated current
exceeds the value of 3,5 Ampere, available at the power supply, the exceeding current, necessary during the Alarm condition, is drawn from
the batteries.
5 The sum of currents obtained must be multiplied by a 1,2 factor to take account of the battery manufacturing tolerances.
AM-8200
AM8200_manu-inst
Table 2
NORMALcondition
A
Q
Current each
Current
(dev x Q)
135 mA
50 mA
28 mA
39 mA
62 mA
0
|_________|
|_________|
|_________|
|_________|
(Max 2A )
0
0
0
|_________|
|_________|
4
Total
=
(x24h) or
(x72h) =
Stand-by (A)
Ah Battery = (A + B) x 1.2
Installation Manual
Doc. M-162.2-AM8200-ENG Rev A.2
ALARM condition
Total
Current each
177 mA
92 mA
28 mA
39 mA
62 mA
0
|_________|
0
|_________|
0
|_________|
0
|_________|
|_________|
Total
=
Ah
Alarm (B)
5
=
B
Total Current (dev
x Q)
|_________|
|_________|
|_________|
|_________|
|_________|
(Max 2A)
|_________|
|_________|
|_________|
|_________|
x 0.5 h =
Ah
Ah
PAGE - 39