POWER SUPPLY – Current calculation
The power supply must be able to continuously power all the internal system devices (and all external devices)
during the stand-by period, that is in NON-alarm conditions.
-
Use the table A to calculate the load in stand-by conditions.
-
Use the table B to calculate the additional current which is necessary in Alarm conditions
A 24 Vcc internal power supply for a total of 4 Ampere is available on the power supply for the system operation
Item
AM-8200
AM-8200 CPU(AM8200-KLCD)
LIB-8200
AM82-2S2C
AM82-BST-C
SIB-8200
Devices connected to Sounder Output
1
2
Loops
Current
Refer to Table 3
Loop 1
Loop 2
Loop 3
Loop 4
User Output current
3
LCD-8200
Bells
Sounders
Strobes
Other devices
PAGE - 38
NOTIFIER ITALIA
Table 1
NORMAL condition
A
Q
Current each
Current
(dev x Q)
179 mA
50 mA
28 mA
39 mA
62 mA
0
|_________|
|_________|
|_________|
|_________|
(Max 2A )
0
0
0
|_________|
|_________|
Total
4
=
(x24h) or
(x72h) =
Stand-by (A)
Ah Battery = (A + B) x 1.2
INSTALLATION MANUAL
Doc. M-162.2-AM8200-ENG Rev A.2
ALARM condition
Total
Current each
345 mA
92 mA
28 mA
39 mA
62 mA
0
|_________|
0
|_________|
0
|_________|
0
|_________|
|_________|
Total
=
Ah
Alarm (B)
5
=
B
Total Current (dev
x Q)
|_________|
|_________|
|_________|
|_________|
|_________|
(Max 2A)
|_________|
|_________|
|_________|
|_________|
x 0.5 h =
Ah
Ah