Download Print this page
F&F AZH-LED Manual

F&F AZH-LED Manual

Twilight switch, hermetic

Advertisement

Quick Links

AZH-LED
Twilight switch,
hermetic
Do not dispose of this device in the trash along with other waste!
According to the Law on Waste, electro coming from households free of charge and can
give any amount to up to that end point of collection, as well as to store the occasion of
the purchase of new equipment (in accordance with the principle of old-for-new, regard-
less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the
environment and human health.
Purpose
The AZH-LED is a twilight switch with a built-in light sensor, enc-
losed in a hermetically sealed housing and specially adapted to
switch on the LED lighting. By using a switching element that gu-
arantees correct operation with current pulses up to 160 A and
additional components responsible for surge suppression, the
AZH-LED will successfully manage to switch on and off the LED
lighting, despite its energy efficiency, generates strong current
surges when switched on, effectively destroying classic relays.
Functioning
The twilight switch should be placed in a place with constant
access to natural light, which by changing its intensity will cau-
se the lighting to switch on and off. The time of switch-on of
the lighting can be set by the user using the potentiometer.
Rotation towards the "moon" – will switch on the lighting later,
rotation towards the "sun" – will switch it on earlier. The twili-
ght switch has a system that delays switching on and off of the
lighting, thus reducing the impact of various disturbances (such
F&F Filipowski sp. j.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl

Advertisement

loading

Summary of Contents for F&F AZH-LED

  • Page 1 Electro thrown in the trash or abandoned in nature, pose a threat to the environment and human health. Purpose The AZH-LED is a twilight switch with a built-in light sensor, enc- losed in a hermetically sealed housing and specially adapted to switch on the LED lighting. By using a switching element that gu-...
  • Page 2 as atmospheric discharges) on the operation of the machine. Mounting 1. Turn off the power supply. 2. Fix the twilight switch vertically (with the cable facing down) to the ground with two screws in a place that is not illuminated by the switched (or other) light source.
  • Page 3 Connection diagram Technical data power supply 195÷253 V AC maximum load current (AC-1) 10 A switch-on threshold (adjustable) 2÷1000 lx histeresis approx. 15 lx activation delay approx. 10 s deactivation delay approx. 20 s resistance to current shocks 160 A/20 ms power consumption 0.56 W terminal...
  • Page 4 Power table tungsten halogen fluorescent energy-saving 1500 W 1000 W 500 W 300 W 300 W The above data are indicative and will heavily depend on the design of a specific receiver (that is especially important for LED bulbs, energy-saving lamps, electronic transformers and pulse power supply units), switching frequency and operating conditions.