en | Connection
Caution!
Compliance with EN50130-4 Alarm Standard – CCTV for Security Applications
To meet the requirements of the EN50130-4 Alarm Standard, an ancillary uninterruptable
!
power (UPS) supply is necessary. The UPS must have a Transfer Time between 2–6 ms and a
Backup Runtime of greater than 5 seconds for the power level as specified on the product
datasheet.
13.3

Ethernet Connections

Caution!
Ethernet cables must be routed through earth-grounded conduit capable of withstanding the
!
outdoor environment.
Cable Type
Maximum Distance
Ethernet
Terminal Connector
High PoE
Note: Consult the National Electrical Code (NEC) or other regional standards for cable
bundling requirements and limitations.
2021-03 | 1.2 |
Cat5e/Cat6 Shielded Twisted Pair (STP) Ethernet (directly to the
camera, or to a network switch between the camera and the network)
Note: Cat5e/Cat6 Shielded Twisted Pair (STP) cable is required in
order to meet European regulatory EMC standards.
100 m (330 ft)
10BASE-T/100BASE-TX, auto-sensing, half/full duplex
RJ45, Male
For models with attached illuminators: Use the 95 W midspan sold by
Bosch.
For models without illuminators: Use the 60 W midspan sold by Bosch,
or a midspan that is compliant to the IEEE 802.3at, class 4 standard.
Installation Manual
MIC inteox 7100i
Bosch Security Systems