State of digital inputs
Relay output control
Analogue input 2 voltage
(V)
Analogue output 2 current
(mA) Models above 7.5kW
only
Local/USS mode
Software version
Equipment system number
13-22
0 - 3F
Read-only. Provides a HEX representation
[-]
of a 6-digit binary number of which the LSB
= DIN1 and the MSB = DIN6 (1 = ON, 0 =
OFF).
e.g. If P723 = B, this represents '001011' -
DIN1, DIN2 and DIN4 = ON, DIN3 , DIN5
and DIN6 = OFF.
0 - 3
Enables control of the output relays. Used in
[0]
conjunction with P720, e.g. setting P724 = 1
(relay 1 = ON) has no effect unless P720 =
1, 3, 5,or 7.
0 = Both relays OFF / de-energised
1 = Relay 1 ON / energised
2 = Relay 2 ON / energised
3 = Both relays ON / energised
0.0-10.0
Read only. Displays the analogue input 2
[-]
voltage (approximate) only when analogue
input 2 is active (P051 to P055 or P356 = 24
and the respective digital input is high).
0.0-20.0
Allows direct control of the analogue output
[0.0]
2 current if P720 = 4, 5, 6 or 7.
0 - 4
Sets the inverter for local control or USS
[0]
control over the serial link:
0 = Local control
1 = Remote control (and setting of
parameter values)
2 = Local control (but USS control of
frequency)
3 = USS control (but local control of
frequency)
4 = Local control (but USS read and write
access to parameters and facility to
reset trips)
When operating the inverter via remote
control (P910 = 1 or 2 ), the analogue input
remains active when P006 = 1 and is added
to the setpoint.
0.00 -
Contains the software version number and
99.99
cannot be changed.
[-]
0 - 255
You can use this parameter to allocate a
[0]
unique reference number to the inverter. It
has no operational effect.
ECO REFERENCE MANUAL