Siemens MICROMASTER Eco Reference Manual page 83

Hvac-frequency inverter
Hide thumbs Also See for MICROMASTER Eco:
Table of Contents

Advertisement

ECO REFERENCE MANUAL
Frequency setpoint (Hz)
Motor current (A)
Motor torque (% nominal
torque)
DC link voltage (V)
Motor RPM
Output voltage (V)
Most recent fault code
Most recent fault code -1
Most recent fault code -2
Most recent fault code -3
PID closed loop mode
P gain
I gain
D gain
Integral gain scaling
Transducer filtering
Integral capture range (%)
0.0-
150.0[-]
0.0 -
300.0
[-]
0 - 250
Read-only parameters. These are copies of
[-]
the values stored in P001 but can be
accessed directly via the serial link.
0 - 1000
[-]
0 - 9999
[-]
0 - 1000
[-]
0 - 255
Read only. The last recorded fault code (see
[-]
'Fault Codes') is stored in this parameter. It
is cleared when the inverter is reset.
This is a copy of the code stored in P930.
0 - 255
Read only. This parameter stores the last
[-]
recorded fault code prior to that stored in
P140/P930.
0 - 255
Read only. This parameter stores the last
[-]
recorded fault code prior to that stored in
P141.
0 - 255
Read only. This parameter stores the last
[-]
recorded fault code prior to that stored in
P142.
0 - 1
0 = Normal operation (closed loop process
[0]
control disabled).
1 = Closed loop process control using
analogue input 2 as feedback.
0.0-999.9
Proportional gain.
[1.0]
0.00-99.9
Integral gain.
[0]
0.0-999.9
Derivative gain.
[0]
1 - 2400
The integral action time is multiplied by this
[1]
value
0 - 255
0 = Filter off.
[0]
1 - 255 = Low pass filtering applied to
transducer.
0 - 100
Percentage error above which integral term
[100]
is reset to zero.
13-19