Siemens MICROMASTER Eco Reference Manual page 59

Hvac-frequency inverter
Hide thumbs Also See for MICROMASTER Eco:
Table of Contents

Advertisement

EMC
Class 2: Filtered Industrial
This level of performance will allow the manufacturer/assembler to self-certify their apparatus for
compliance with the EMC directive for the industrial environment as regards the EMC performance
characteristics of the power drive system. Performance limits are as specified in the Generic Industrial
Emissions and Immunity standards EN 50081-2 and EN 50082-2.
Emissions:
Radiated Emissions
Conducted Emissions
Immunity:
Supply Voltage Distortion
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
Magnetic Fields
Electrostatic Discharge
Burst Interference
Radio Frequency Electromagnetic Field,
amplitude modulated
Radio Frequency Electromagnetic Field,
pulse modulated
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify compliance of their
apparatus with the EMC directive for the residential, commercial and light industrial environment as
regards the EMC performance characteristics of the power drive system. Performance limits are as
specified in the generic emission and immunity standards EN 50081-1 and EN 50082-1.
Emissions:
Radiated Emissions
Conducted Emissions
Immunity:
Electrostatic Discharge
Burst Interference
The MICROMASTER Eco and MIDIMASTER Eco units are intended exclusively for
professional applications. Therefore, they do not fall within the scope of the harmonics
emissions specification EN 61000-3-2.
12-4
EMC Phenomenon
EMC Phenomenon
Standard
EN 55011
Level A1
EN 55011
Level A1
IEC 1000-2-4 (1993)
IEC 1000-2-1
EN 61000-4-8
50 Hz, 30 A/m
EN 61000-4-2
8 kV air discharge
EN 61000-4-4
2 kV power cables, 2 kV control
ENV 50 140
80-1000 MHz, 10 V/m, 80% AM,
power and signal lines
ENV 50 204
900 MHz, 10 V/m 50% duty cycle,
200 Hz repetition rate
Standard
EN 55022
Level B1
EN 55022
Level B1
EN 61000-4-2
8 kV air discharge
EN 61000-4-4
1 kV power cables, 0.5 kV control