Connection Example; Line Supply/Load Connection - Siemens SINAMICS S120 Equipment Manual

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
4.2 Basic Line Modules
4.2.3.2

Connection example

Fig. 4-4
4.2.3.3

Line supply/load connection

Table 4-1
Line/load connection for the Basic Line Module
Terminals
U1, V1, W1
3 AC power input
DCP, DCN
DC power output
PE connection
4-6
ext.
24 V
Main breaker /
circuit breaker
Main contactor
L3
L2
L1
Line filters
L3'
L2'
L1'
1W1
1V1
1U1
Line reactors
1W2 1V2
1U2
Wiring diagram for the Basic Line Module
Technical specifications
Voltage:
380 V 3 AC –10 % to 480 V 3 AC +10 % (-15 % < 1 min)
500 V 3 AC –10 % to 690 V 3 AC +10 % (-15 % < 1 min)
Frequency: 47 Hz to 63 Hz
Connecting thread M12 / 50 Nm for ring cable lugs to DIN 46234
Voltage:
513 V to 648 V DC
675 V to 932 V DC
Connecting thread M12 / 50 for ring cable lugs to DIN 46234
Connecting thread M12 / 50 for ring cable lugs to DIN 46234
X9
+
1
+24 V
1
2
M
M
2
3
Reserved, do not use
4
Reserved, do not use
5
Main contactor control
6
7
EP +24 V
8
EP M1
Basic Line Module
X41
4
Do not use
3
Do not use
2
EP +24 V
1
EP M1
X42
8
P24V
7
M
6
U24V
5
U0V
4
PH_RS
3
PH_ST
2
PH_TR
1
M
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2
X400
X401
X402
DCP
DCN
H200
H201
Chassis Power Units Liquid Cooled

Advertisement