Application Guidelines

50 Hz

Model
HP
MLM116
15
MLZ116
15
Note: EN12900 conditions: To= -10°C, Tc= 45°C, RGT= 20°C, SC= 0K

Technical specifications

Nominal
Power
cooling capacity
input
W
Btu/h
kW
24451
83427
10789
26865
91664
12127
Efficiency
Swept volume
COP
EER
W/W
Btu/h/W
cm3/rev
2.27
7.73
249.9
2.22
7.56
249.9
Single compressors
Net weight
Displacement
Oil charge
(with oil)
m3/h
Litres
43.5
6.7
43.5
6.7
FRCC.PC.035.A5.02
kg
100
100
9