Starting Procedures - IAI RCON-GW First Step Manual

Gateway unit, terminal unit

Advertisement

5. EtherNet/IP (RCON-GW/GWG-EP)
7. PROFINET IO (RCON-GW/GWG-PRT)
Refer to the instruction manuals for each field network master unit and mounted PLC for the details.
Connector Name
EtherNet/IP, PROFINET IO Connector
Cable Side
Ethernet ANSI/TIA/EIA-568-B Category 5
and above 8P8C modular plug equipped
1
with shield (RJ45)
Controller Side
Ethernet ANSI/TIA/EIA-568-B Category 5
and above 8P8C modular Jack equipped
with shield (RJ45)
8
Pin
Signal Name
Description
Top View of
No.
Connector on
1
TD+
Data sending+
Controller side
2
TD-
Data sending-
3
RD+
Data receiving+
4
-
Disconnected
5
-
Disconnected
6
RD-
Data receiving-
7
-
Disconnected
8
-
Disconnected
Switching Hub
Master Unit
Ethernet Straight Cable,
Category 5 or more
Double shielded cable braided with
aluminum foil recommended
6. PROFIBUS-DP (RCON-GW/GWG-PR)
Refer to the instruction manuals for each field network master unit and mounted PLC for the details.
Red B line (Positive side)
Green A line (Negative side)
1
6
Cable
9
5
Shield
Connector Name
PROFIBUS-DP Connector
Top View of
Cable Side
9-pin D-sub Connector (Male)
Connector on
Controller side
Controller Side
9-pin D-sub Connector (Female)
Pin
Signal Name
Description
No.
1
NC
Disconnected
2
NC
Disconnected
3
B-Line
Communication Line B (RS485)
4
RTS
Request for Sending
5
GND
Signal GND (Insulation)
6
+5V
+5V Output (Insulation)
7
NC
Disconnected
8
A-Line
Communication Line A (RS485)
9
NC
Disconnected
Master Unit
Slave Devices
Grounding resistance at 100Ω or less
(Class D grounding)
In this controller, it is available to select six types of operation modes individually for each axis as the field
network type.
The settings are to be established with Gateway Parameter Setting Tool.
Operation Mode
Remarks
Please prepare
Direct Indication
separately
Mode
Simple Direct Mode
Applicable cable
diameter
Positioner 1 Mode
It is recommended
Positioner 2 Mode
to prepare a
straight STP cable
in Category 5 or
above for the
Ethernet cable.
Positioner 3 Mode
Positioner 5 Mode
Slave Devices
When using this product for the first time, make sure to avoid mistakes and incorrect wiring by referring to
the procedure below.
In this section, explains how to start up especially for RCON controller. Follow an instruction manual (DVD)
for each device for how to link to other devices, controllers and actuators that are linked in the network.
RCON-
EtherNet Type
Check of Packed Items
or
Are all the delivered items present?
RCON-
↓Yes
PROFINET IO Type
Assembling RCON (Linking up Units) * Refer to RCON 24V/200V Driver Unit First Step Guide (ME0383/ME0397)
Join the units to use such as the gateway unit, driver unit, extension unit and so on.
Installation and Wiring
* Refer to [Installation and Noise Elimination] in this first step guide
Install the controller and actuator and perform wiring according.
Initial Settings (Setup of Gateway) * Gateway parameter setting tool is required
Have the settings done for the axis number setting, mode settings, field network communication speed, node addresses
(station numbers) and so on to suit to the system.
Initial Settings (Setup of Driver Units and Extension Units) * RC PC software is required
Remarks
Establish the parameter settings for each controller.
Please prepare separately
PLC (Master Unit) Baud Rate * Refer to PLC Instruction Manual.
Have the settings established for the PLC node addresses (station
numbers) and the baud rate.
Applicable cable diameter
Power Supply
1) Supply the power to PLC (master unit).
2) In case of using the extension units, turn the power on for SCON connected to the extension units.
3) Supply the power to RCON.
Dedicated cable for
PROFIBUS-DP
(Type A: EN5017)
Communication Establishment Check
• In case of using the extension units, turn the power on for SCON
connected to the extension units.
* Refer to "Troubleshooting" in this first step guide
• Confirm that communication is established also on PLC (master unit).
* Refer to PLC Instruction Manual.
RCON PROFIBUS-DP Type
↓Yes
Check on Safety Circuit
Confirm that the stop circuit (drive source cutoff circuit) works in normal conditions.
↓Yes
Now, it is succeeded to establish communication and ready for operation.
Move on to the system operation check and adjustment.
Operation Mode Selected
Contents
The target position, speed, acceleration/deceleration and pressing current limit can be
indicated with inputting a number. Monitoring of not only the current position, but also
the current speed and indicated current are available.
The target position can be indicated directly by inputting a value. Also, monitoring of the
current position is available in 0.01mm unit.
Those other than the target position are to be indicated in the position table, and the
setting can be done for 128 points at maximum.
The 128 points of position data can be registered at the maximum and is able to stop at
the registered positions. Also, monitoring of the current position is available in 0.01mm
unit.
This is the operation mode of the position data of 128 points at maximum set in the
position table. The monitoring of the current position is not available.
This mode is that the transferred data is reduced from Positioner 1 Mode.
This is the operation mode of the position data of 128 points at maximum set in the
position table. The monitoring of the current position is not available.
This is the mode to control with the minimized number of signals to perform the
positioning operation by reducing the amount of sent and received data from Positioner
2 Mode.
This is the operation mode of the position data of 16 points at maximum set in the
position table.
It is a mode that enabled to monitor the current position in 0.1mm unit by reducing the
number of position table from Positioner 2 Mode.

Starting Procedures

No →
Contact your local IAI distributor
Important Check Item
• Is frame ground (FG) connected?
• Has the noise countermeasure been taken?
← Yes
Important Check Item
• Is the control sequence applicable for
the continuous mode and the system?
Check the status of LED lamps to see the
No →
cause of the error to have an appropriate
counteraction. Do the whole process from
the start if the cause of the error is not
clear.
No →
Check the circuit.
Troubleshooting (LED Display)
On RCON Gateway Unit, there are the monitor LEDs for the field network and communication.
You can confirm the communication establishment and also communication errors on these LEDs.
Refer to "Names for Each Part" for the position and name of each LED lamp.
Panel
Color
Status
Display
Illuminating
Inside bus communication in normal conditions
GN
T RUN
Flashing
Waiting for initializing communication
OR
Illuminating
Inside bus communication in error
GN
Illuminating
Operating in normal conditions
SYS
OR
Illuminating
Gateway alarm being generated
Confirmed STOP Signal input
Illuminating
(driver unit drive source being cut off)
STOP
RD
OFF
No STOP Signal input confirmed
Illuminating
In AUTO (automatic operation) Mode
MODE
GN
OFF
In MANU (manual operation) Mode
Illuminating
Error occurred in field network
C ERR
OR
OFF
Field network operating in normal conditions
Differs depending on field network (Refer to Field Network
STATUS 0
-
-
Communication Conditions from 1 to 7)
Differs depending on field network (Refer to Field Network
STATUS 1
-
-
Communication Conditions from 1 to 7)
[Field Network Communication Conditions]
1. CC-Link (RCON-GW/GWG-CC)
Panel
Name
Color
Status
Display
Succeeded in refresh and polling reception after
Illuminating
getting into network, or succeeded in refresh
reception
STATUS 0
RUN
GN
1. Not in network
2. Carrier detected for channel
OFF
3. Timeover
4. In hardware reset
1. CRC Error
2. Station number setting error at reset release
(65 stations or more including 0 or occupied
Illuminating
station number)
3. Baud rate setting error at reset release
(5 or more for baud rate setting)
STATUS 1
ERR
GN
Flashing
Numbers changed from station numbers and
(Flash for
baud rate setting numbers at reset release
0.4sec)
1. Communication in normal conditions
OFF
2. In hardware reset
2. CC-Link IE Field (RCON-GW/GWG-CIE)
Panel
Name
Color
Status
Display
Illuminating
Operation in normal conditions
GN
OFF
Hardware error occurred
STATUS 0
MS
Illuminating
Error being occurred
OR
OFF
Operation in normal conditions
Illuminating
Cyclic transmission in process
GN
Flashing
Cyclic transmission paused
STATUS 1
NS
OFF
Cyclic transmission not conducted, parallel off
Illuminating
Received data in error
OR
OFF
Received data in normal conditions
Illuminating
Linkup in process
LINK
-
GN
OFF
Link-down in process
Illuminating
Received data in error
L.ER
-
OR
OFF
Received data in normal conditions
Explanation
Explanation
Explanation