General Information
Removing and Reinstalling Front Enclosure Panel and Cover Panel
6
Some of the following start-up/service steps require the
removal of the front enclosure panel and the cover panel.
To avoid personal injury and/or product damage of any
kind please follow the instructions below carefully when
removing or reinstalling the front enclosure panel and

cover panel.

To remove front enclosure panel and cover panel proceed
as follows:
1. Close main gas supply valve.
2. Open flip-down cover of front enclosure panel (by
exerting slight pressure with fingertip) and switch
off system on/off switch.
3. Turn off power supply to boiler and ensure that
power supply cannot be activated during the duration
of the start-up/service work.
4. Unlock enclosure panel by giving cover lock
a quarter turn.
5. Remove burner cover panel by unlocking the two
pull-down latches located on the bottom of the panel,
and slide out panel.
6. Attach front enclosure panel.
7. Secure in place by rotating slotted screw.
Vitodens 200 WB2 Service