SAMUEL JACKSON Argus Installation And Resource Manual page 27

Fire detection system
Table of Contents

Advertisement

Trouble Condition
Red Alarm light stays illuminated:
Trouble light constantly on:
Trouble light blinking:
Alarm LED will not light during detector light
test:
Trouble light will not illuminate:
Power LED will not illuminate:
Trouble buzzer will not sound off:
Trouble LED will not illuminate:
Trouble buzzer sounds off intermittently:
Argus Installation and Resource Guide
Probable Cause
• Detector bad/improperly connected.
• Detector is still sensing fire.
• Detector latched in alarm.
• Zone Card bad/improperly connected.
• Open detector circuit.
• Open bell circuit.
• Open solenoid circuit.
• Wrong end-line resistance.
• Bad Alarm/Monitor Card.
• Buzzer silence switch in wrong position.
• Intermittent connection to detector.
• Bad Zone Card.
• Bad detector.
• LED burned out.
• Bad Zone Card.
• Fuse blown.
• LED burned out.
• No power.
• Fuse blown.
• LED burned out.
• Silence switch off.
• Bad buzzer.
• Bad detector.
• Detector shorted.
• Bad 24V power supply.
MAINTENANCE