Extinguisher
Trouble
2.5
WIRING RELAYS
Wiring relays involves connecting two wires to the zone card terminal block. Connect
terminal 5 to A1 and connect terminal 6 to A2, according to the figure below.
1
End of
-
2
line
oUT
Module
3
+
AnUC
Ground
• Consult your electrician about tying the relay to equipment that needs to shut
down automatically.
• If a relay needs to be replaced, Samuel Jackson supplies a triple pole double
throw 24V DC relay that is rated to 10 amps.
Note: The resistor between 11 and 12 should be left in place.
Argus Installation and Resource Guide
Disconnect switch
AnUC
Terminal block
Detector Circuit
1
1
-
-
2
2
oUT
oUT
3
3
+
+
AnUC
AnUC
Ground
Ground
Figure: Alarm relay wiring
field Wiring
REl/EXT DIsC
1
-
In
+
2 AMP
DET
Terminal block
1
2 3 4 5 6 7 8 9 10 11 12
black
1
-
White
2
oUT
Red
3
+
Green
AnUC
Ground
figure 8.2
Zone Card
84020 REV A
INSTALLATION
12
-
-
-
+
nC
+
nC
+
REl
AUX
EXT
Card static Maximum Power Consumption:
A2
30mA Regulated
A1
1mA Unregulated
Maximum Detector Per Control Panel:
Z-10 - 60 Argus 343 Detectors
Z-20 - 120 Argus 343 Detectors
Maximum Detectors Per Zone:
Argus 343 Detectors - 16
Extinguisher
2 AMPs
EXT
(fUsED
-
+
page: 12
15