General data
Series
Weight
Housing material
Connection terminals
Ʋ Type of terminal
Ʋ Wire cross-section
Voltage supply
Operating voltage
Ʋ Nominal voltage AC
Ʋ Nominal voltage DC
Max. power consumption
Sensor circuit
Number of sensors
Input type
Terminal voltage
Off-load voltage
Short-circuit current
Residual ripple
Processing circuit
Quantity
Type of output
Off-load voltage
Residual ripple of the output current
Current on the input in case of short-
circuit
Current without connected sensor
Ʋ In the range of +20 ... +60 °C
(+68 ... +140 °F)
Ʋ In the range of -20 ... +20 °C
(-4 ... +68 °F)
Max. connectable load
Deviation
Reference conditions
Linearity
16
Module unit for mounting on carrier rails 35 x 7.5 acc. to
EN 50022/60715
160 g (5.14 oz)
Polycarbonate PC-FR
Screw terminal
0.25 mm² (AWG 23) ... 2.5 mm² (AWG 12)
24 ... 230 V (-15 %, +10 %) 50/60 Hz
24 ... 65 V DC (-15 %, +10 %)
3 W (15 VA)
1 x 4 ... 20 mA/HART (5x HART multidrop)
Active (sensor power supply by VEGATRENN 141)
21 ... 16.5 V with 4 ... 20 mA
24 V (+/- 1 V)
< 26 mA
< 50 mV RMS
1 x 4 ... 20 mA/HART
active
< 16.5 V
< 50 µA RMS
< 10 µA
< 50 µA
< 200 µA
600 Ohm
Calibration temperature 25 °C (77 °F)
< 0.1 %
VEGATRENN 141 • 4 ... 20 mA/HART