4 Mounting

4
Mounting
4.1

Mounting instructions

VEGATRENN 141 is designed for carrier rail mounting (top hat rail
35 x 7.5 according to DIN EN 50022/60715). Due to its protection
rating of IP 20, the instrument is suitable for mounting in switching
cabinets. It can be mounted horizontally and vertically.
Note:
When several instruments are mounted together without space in
between, the ambient temperature at the installation location of the
instrument must not exceed 60 °C. Around the ventilation slots there
must be a distance of at least 2 cm to the next component.
VEGATRENN 141 is a corresponding, intrinsically safe equipment
and must not be installed in hazardous areas. A safe operation is only
ensured if the operating instructions and EG type approval certificate
are observed. VEGATRENN 141 must not be opened.
A distance of 50 mm to the intrinsically safe terminals must be en-
sured when mounting.