EXCEL 500/600 - INSTALLATION INSTRUCTIONS
Fig. 66. Connecting to a screw terminal
IMPORTANT
If there already are additional transformers, for
example supplying actuators or active sensors,
connect the 24 Vac (-) (secondary side) of the
transformers together.
8. Attach the terminal blocks to the housing as shown in
Fig. 67.
EN1R-1047GE51 R0913
Fig. 67. Attaching screw terminal block
Table 14. Accuracy of analog input sensors
range
-58 to –4 °F (-50 to –20 °C)
-4 to 32 °F (-20 to 0 °C)
32 to 86 °F (0 to 30 °C)
86 to 158 °F (30 to 70 °C)
158 to 212 °F (70 to 100 °C)
212 to 266 °F (100 to 130 °C)
266 to 302 °F (130 to 150 °C)
28
measurement error
(without sensor tolerance)
Pt1000
NTC (20k ohms)
1.2 K
5.0 K
0.7 K
1.0 K
0.5 K
0.3 K
0.7 K
0.5 K
1.2 K
1.0 K
1.2 K
3.0 K
1.2 K
5.5 K