13.5.2 To clean the water filter in case of trouble

ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
a
b
a Clip
b Magnetic filter/dirt separator
8 Remove the water filter.
9 Remove the drain hose from the water filter.
CAUTION
Although the water circuit is drained, some water may be spilled when removing the
magnetic filter/dirt separator from the filter housing. ALWAYS clean up spilled water.
1 Remove the water filter from the unit. See
4
filter" [
 208].
CAUTION
To protect the piping connected to the magnetic filter/dirt separator from damage it
is recommended to perform this procedure with the magnetic filter/dirt separator
removed from the unit.
2 Unscrew the bottom of the water filter housing. Use an appropriate tool if
needed.
CAUTION
Opening the magnetic filter/dirt separator is ONLY required in case of severe issues.
Preferably this action is never to be done during the complete lifetime of the
magnetic filter/dirt separator.
b
a
a Bottom part to be unscrewed
b Water filter housing
3 Remove the strainer and the rolled‑up filter from the water filter housing and
clean with water.
4 Install the cleaned rolled‑up filter and strainer in the water filter housing.