3. Specifi cations
Model
Heat exchange system
Heat exchange element material
Cladding
Heat insulating material
Motor
Blower
Filter material
Applicable air condition of setting envi-
ronment
Applicable air condition range of outdoor
and indoor
Functions
Weight
Frequency / Power source
Ventilation mode
Fan speed (230 V)
Current
Power Consumption
Air volume
External static pressure
Temperature exchange effi ciency
Enthalpy exchange
effi ciency [%]
Measured at 1.5 m under the center
Noise [dB]
of panel in an anechoic chamber
Starting current
Insulation resistance
Dielectric strength
Air-to-air Total heat exchange (sensible heat + latent heat exchange)
Partition spacing plate-special treated paper
Galvanized steel sheet
Self-extinguishing urethane foam
DC brushless motor. Two units
220 mm diameter. Centrifugal fan
Non-woven fabrics fi lter (Gravitational method 82%, EU-G3)
The setting air condition shall be between -10°C to 40°C, 80%RH or less.
OA temperature shall be -15°C to 40°C, 80%RH or less, with general air
conditioning room environment.
Lossnay ventilation fi ve speeds / Bypass ventilation (fi ve speeds + power)
48 kg
50 Hz / Single phase 220 to 240 V
Lossnay (Energy recovery) ventilation
1
2
[A]
1.17 0.67 0.35 0.20 0.13 1.80 1.20 0.70 0.35 0.20 0.13
[W]
165
90
[m
/h]
395
305
3
[l/s]
110
85
[mmH
O] 10.2
6.1
2
[Pa]
100
60
[%]
77.5 81.5 85.5
Heating
71
75
Cooling
68
72.5
31
26.5
2.5 A or less
10 MΩ or more (500 V megger)
AC 1500 V 1 minute
LGH-50RSDC-E1
3
4
5
Power
41
22
14
265
215
144
90
468
60
40
25
130
3.1
1.5
0.7
13.8 10.2
30
15
7
135
88
90
79
82
84
77
80.5
83
21
18
18
35
─ 5 ─
1
Bypass ventilation
1
2
3
164
90
40
395
305
215
110
85
60
6.1
3.1
100
60
30
-
-
-
-
-
-
-
-
-
-
-
-
31
26.5
21
4
5
21
14
144
90
40
25
1.5
0.7
15
7
-
-
-
-
-
-
18
18