Badger Meter Data Industrial 340 BN/MB Installation & Operation Manual page 21

Btu energy transmitter, hydronic energy transmitter with rs-485 bacnet and modbus and scaled pulse output
Table of Contents

Advertisement

Modbus Register Map
July 2012
Model 340BN/MB Register Map
Register Name
Address
Temperature 1
40001 + 40002
Temperature 2
40003 + 40004
Flow Input (Hz)
40005 + 40006
Total Flow
40007 + 40008
Total Energy
40009 + 40010
Flow Rate
40011 + 40012
Energy Rate
40013 + 40014
K Factor
40015 + 40016
Offset
40017 + 40018
Temp Calc Mode
40019 + 40020
Flow Filter Coef
40021 + 40022
Temp Filter Coef
40023 + 40024
Specific Heat
40025 + 40026
Fluid Density
40027 + 40028
T1 A Coefficient
40029 + 40030
T1 B Coefficient
40031 + 40032
T1 C Coefficient
40033 + 40034
Temp 1 Offset
40035 + 40036
T1 A Coefficient
40037 + 40038
T1 B Coefficient
40039+ 40040
T1 C Coefficient
40041 + 40042
Temp 1 Offset
40043 + 40044
Data Type
Read/Write
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only
IEEE 754 Float
Read Only