5.8 Stopping the engine
1. Before stopping the engine, unload first, decrease the engine to the idle speed
gradually, also cut off the clutch system. When the water temperature falls down
below 70°C, operate the stop handle to stop to stop the engine.
2. After stopping, should take the circuit switch, close the fuel tank valve.
3. When the temperature under 0℃, if do not use the antifreeze, should drain out the
cooling water from the engine to avoid damage the engine body and water pump. If
with antifreeze, it is unnecessary to drain out the water.
Note: Do not stop the engine by shutting off the valve of the fuel tank!
Do not stop the engine suddenly at high water temperature.
Do not stop the engine at high speed over 1000RPM!
5.9 Run in Operation rule for the new diesel engine
The new engine´s operating life period, working stability and economics, mainly depends
on previous adjusting period. Thus user should operate the engine under the:
"New engine adjusting principle".
Number
Load
1
Idle load
2
25% load
3
50% load
4
75% load
5
100% load
6
total
Running
time
1) During adjusting period, fuel valve
10 min.
should at full open position , load can
2 hours
be estimated by left load form , but
must know the principle of increasing
15 hours
load gradually .
30 hours
2) During running period , pay attention
to water temperature, oil pressure, oil
45 hours
increasing temperature . Listen
carefully for strange sound. If any
60 hours
problem, stop engine and remedy
immediately .
Note
16