5.2 Restoring power outputs

As discussed in the Welcome section, the Central Power Hub ports are carefully monitored to ensure safety protection while also
maintaining power consistency to the multiple devices:
• Electronic short protection - If an overload or short circuit occurs on any output, the power is limited to a safe value (by current
pulsing) until the microprocessor recognizes the overload condition and trips the output – this happens approximately one sec-
ond after the fault happens. The resulting trip is indicated on the Central Power Hub front panel by the OVLD being on and
also within the management application ('FAULT' is shown next to the affected port within the Status & Control page).
• 5V overload protection - Applicable only to outputs that use optional Converter dongles. When the load exceeds approximately
5.5A*, a dongle will internally trip its power output. In most cases this will occur before the electronic short protection (men-
tioned above) reacts. In such cases, the power trip will not be reported back to the Central Power Hub unit and its output will
remain intact, although the listed current output for that port will fall to (or near) zero.
5.2.1 To restore a power output
1 Following an automatic power trip, your first task is to locate the cause of the problem. It may have been a temporary overload
issue that has subsided or something more permanent. Perform thorough checks on the implicated device and all of the power
cabling between it and the Central Power Hub.
2 Depending on where the trip was made, you will see different results:
• If the Central Power Hub electronic short protection circuit responded, the front panel
rear panel green indicator adjacent to the affected port will be OFF. Within the Status & Control page of the manager appli-
cation, the port State will be shown as FAULT.
• If the converter dongle overload circuit responded, it is likely that the corresponding Central Power Hub output port will still
be active.
3 Accordingly, your remedial actions will differ:
• Where the fault is indicated on the front panel
narrow implement (e.g. straightened paperclip) to press and release the recessed front panel CLEAR button. The power out-
put to port will be reinstated. Alternatively, within the management application (Status & Control page), click the FAULT
state shown against the affected port.
• Where the fault was detected by a converter dongle, either use the Status & Control page of the management application
to switch the port Off and then On; or at the Central Power Hub rear panel remove and reconnect the converter dongle
connection.
4 For a suitable period after resuming the power supply to the affected port, closely monitor the device, the Central Power Hub
and all related cabling for a reoccurrence of the same or similar problem.
* If you are using the management application to monitor supply currents, remember that due to the conversion from 12VDC to
5VDC, the values shown at the power output ports (within the app) differ from the currents flowing to the device. Roughly
speaking, 5.5A at the 5V level will be reported at the management application as 2.3A at 12V.
Page 22
OVLD
indicator (once you have diagnosed and corrected the cause), use a
877-877-2269 | blackbox.com
OVLD
indicator will be lit and also the

Advertisement

Table of Contents
loading

Table of Contents