3.3 Fitting/removing a power module

The Central Power Hub main chassis can accommodate two power modules, although operation is perfectly possible with just
one module fitted. The addition of a second module provides redundancy for critical installations.
IMPORTANT: To ensure correct and reliable operation, only approved power modules may be used with the Central
Power Hub. Upon startup, each inserted power module is interrogated by the Central Power Hub and only those that
present the correct identity code will be energized. If a non-authorized power module is inserted, the
tor will illuminate and the corresponding
flash.
Note: Module bay 1 is on the left as you view the rear of the Central Power Hub chassis, module bay 2 is on the right.
3.3.1 To fit a power module
Note: Power modules are hot-pluggable (i.e. while power is applied to the other mod-
ule), be sure to observe safe working practices and anti-static precautions when fitting a
module to a working Central Power Hub chassis.
1 If a blanking plate is fitted, remove it to reveal the power module bay.
2 Observing suitable anti-static precautions, remove the new power module from its
packing.
3 Carefully slide the power module into the vacant bay until the locking clip 'clicks' to
hold the module in place.
4 Insert an IEC power cord into the socket on the module and apply power to
the module.
3.3.2 To remove a power module
Note: Power modules are hot-pluggable (i.e. while power is applied to the other module), be sure to
observe safe working practices and anti-static precautions when removing a module from a working
Central Power Hub chassis.
1 Isolate power from the module to be removed and disconnect the IEC power cord.
2 Push the locking lever to the left so that the module un-clips and use the handle to carefully pull
the module out of the bay.
3 If no replacement module is to be used, fit a blanking plate to cover the vacant bay.
IMPORTANT: Please read and adhere to the electrical safety information given within the Safety information section of this
guide. In particular, do not use an unearthed power socket or extension cable.
Note: Various items within the Central Power Hub casing generate heat when in operation and will become warm to the touch.
Ensure that air can circulate freely at the rear of the enclose, particularly by the power module cooling fans. Do not operate the
equipment in ambient temperatures exceeding 50 degrees Centigrade. Do not place the products in contact with equipment
whose surface temperature exceeds 50 degrees Centigrade.
P1
or
P2
indicator (as well as the indicator on the power module itself) will
877-877-2269 | blackbox.com
Chapter 3: Installation
INVLD
indica-
Page 11

Advertisement

Table of Contents
loading

Table of Contents