Quick Start Guide
PN/EtherNetIP Coupler
Order number: 700-160-3EN02
Helmholz GmbH & Co. KG | Hannberger Weg 2 | 91091 Großenseebach | Germany
Phone +49 9135 7380-0 | Fax +49 9135 7380-110 | info@helmholz.de | www.helmholz.de
Version
3
en
13.08.2020

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PN/EtherNetIP Coupler and is the answer not in the manual?

Questions and answers

Summary of Contents for Helmholz PN/EtherNetIP Coupler

  • Page 1 Quick Start Guide Version PN/EtherNetIP Coupler Order number: 700-160-3EN02 Helmholz GmbH & Co. KG | Hannberger Weg 2 | 91091 Großenseebach | Germany 13.08.2020 Phone +49 9135 7380-0 | Fax +49 9135 7380-110 | info@helmholz.de | www.helmholz.de...
  • Page 2: Table Of Contents

    Assign a name to the PN/EtherNetIP coupler ................. 7 Configuration in Rockwell Studio ................. 8 Access the website and download the EDS file ................8 Load EDS file and configure the PN/EtherNetIP coupler ..............9 Status and control via the PLC ................11 Status ............................11 Control ............................
  • Page 3: Introduction

    QR code directly. 3 Function of the PN/EtherNetIP Coupler With the PN/EtherNetIP Coupler, a simple and uncomplicated connection of a PROFINET machine to an EtherNet/IP machine is possible. The PN/EtherNetIP Coupler allows data transmission between a PROFINET controller and an EtherNetIP scanner.
  • Page 4: Connection

    "X2 P1" and "X2 P2" are used to connect the EtherNet/IP network. The PN/EtherNetIP coupler must be connected to the wide range input DC 18 ... 30 V via the supplied connector plug, the PN/EtherNetIP Coupler must be supplied with DC 24 V. The power supply is designed redundantly, at least one supply path PS 1 or PS 2 must be connected.
  • Page 5: Configuration In Tia Portal

    6 Configuration in TIA Portal The data exchange between the PROFINET and the EtherNet/IP side of the PN/EtherNetIP coupler is defined exclusively via the Simatic Engineering Tool. New EtherNet/IP assemblies can be created in the slots of the PROFINET configuration and I/O data of the PROFINET PLC can be assigned to these assemblies.
  • Page 6: Parameters Of The Pn/Ethernetip Coupler

    EtherNet/IP product name / DHCP hostname: Name of the device EtherNet/IP product code: Number of the device in the EtherNet/IP network. The number is used in the EDS file. If more than one PN/EtherNetIP coupler is used in an EtherNet/IP network, this code must be different for each device! Data alignment in assemblies: If the EtherNet/IP PLC cannot address data by byte alignment it is possible to force the Coupler to align the data to word or double-word addresses.
  • Page 7: Assign A Name To The Pn/Ethernetip Coupler

    To enable the PN/EtherNetIP Coupler to be found by the PROFINET controller, the PROFINET device name must be assigned to the PN/EtherNetIP Coupler. To do this, use the "Assign device name" function, which you can access with the right mouse button or in the Online menu if the PN/EtherNetIP Coupler is selected.
  • Page 8: Configuration In Rockwell Studio

    7.1 Access the website and download the EDS file As soon as the PN/EtherNetIP Coupler has been configured via the PROFINET PLC, the website of the device can be accessed via the PROFINET network. If the IP address is also available on the EtherNet/IP network side (Static-IP, DHCP successful), the website can also be accessed via the EtherNet/IP network.
  • Page 9: Load Eds File And Configure The Pn/Ethernetip Coupler

    "Module config" menu. The current transferred data is also displayed here. 7.2 Load EDS file and configure the PN/EtherNetIP coupler Import the EDS file into the Studio 5000 with the function "EDS Hardware Installation Tool" in the menu "TOOLS".
  • Page 10 The Rockwell Studio can manage assemblies of up to 500 bytes. If more data is to be exchanged between the PROFINET PLC and the EthernetIP PLC, additional assemblies must be created. QuickStart Guide PN/EtherNetIP Coupler | Version 3 | 13.08.2020...
  • Page 11: Status And Control Via The Plc

    Byte 1 Number of active EtherNet/IP connections 8.2 Control The PN/EtherNetIP coupler can be controlled via the following control bits (1 byte) in the PROFINET output image Byte/Bit Disable EtherNet/IP Byte 0 EtherNet/IP Reset connections...
  • Page 12: Mqtt Publisher

    9 MQTT Publisher The PN/EtherNetIP Coupler provides PROFINET / EtherNetIP communication as well as an MQTT Publisher. MQTT is a widely used and simple protocol for distributing information in large networks. The MQTT Publisher can be activated via the PROFINET configuration on the PROFINET or EtherNetIP interface.
  • Page 13: Technical Data

    CE, PROFINET Conformance Class B (in preparation) Protection rating IP 20 Relative humidity 95% non-condensing Mounting position Ambient temperature 0° C to 60° C Transport and storage temperature -20° C to 80° C QuickStart Guide PN/EtherNetIP Coupler | Version 3 | 13.08.2020...
  • Page 14: Led Status Information

    They are also provided in our download area of the respective products under www.helmholz.de. We also offer to send you or any third party the complete corresponding source text of the respective open source software for an at-cost fee of 10.00 Euro as a DVD upon request. This offer is valid for a period of three years, starting from the date of product delivery.