Discharge Device - Baur PGK 50 Operating Instructions Manual

High voltage testing sets
Table of Contents

Advertisement

Discharge device

25
22.5
20
17.5
15
12.5
10
7.5
5
2.5
0
0
5
The discharge device of the PGK50/80 consists of a pressure tank
(overpressure = 3 bar) filled with insulatig gas (SF
hexafluoride). A NC-contact and a discharge resistor are installed in
the pressure tank. The discharge resistance is 69k including
transient protection and is configured for a maximum surge power
of 8.000Ws.
The discharge device works automatically and independent of
instrument position and remains activated even at power
failure.The response of the discharge device is a loud switching
noise.
Diagram 1 indicates the maximum permissable load capacitance
Diagram 1
depending upon the selected test voltage.
10
15
20
25
30
During two discharges:
With discharges < 8000 Ws:
After completion of a test wait at least 10 seconds after the
switching noise of the discharge device. Therafter handle the
test object as follows:
1. Discharge with discharge rod,
2. Ground,
3. Short out!
Do not open discharge device. Servicing the Testing Set may
only be performed by instructed service personnel.The local
rules and regulations regarding handling of SF
observed.
35
40
45
50
55
Observe 15 minute pause time!
Reduce pause time accordingly!
1. Product Information
sulphur
6
60
65
70
75
80
Test voltage in kV
gas must be
6
1-3