26 Parameter settings
Index
Name
POUS.02
POUS acknowledge-
ment
POUS.11
POUS input
POUS.13
POUS delay for com-
pletion
POUS.21
POUS output
POUS.22
POUS completed
output
I/O parameters
SAFEIO.35
DI X113:3 Diag pulse
on/off
SAFEIO.39
DI X114:3 Diag pulse
on/off
Example value
Description
Automatic
Sets the POUS acknowledgement method.
Set this parameter according to the applica-
tion requirements.
Automatic: The FSO module generates the
POUS acknowledgement signal automatic-
ally after the POUS request signal is re-
moved.
Manual: The FSO module reads the POUS
acknowledgement signal through the digital
input defined by parameter FSOGEN.42
Acknowledgement button input. The FSO
module accepts the acknowledgement after
the POUS request is removed.
If you set this parameter to Manual, you
must implement a manual acknowledgement
for the POUS function.
DI X113:3 & X114:3
Sets the digital input that is connected to
the POUS input.
For option +Q950, ABB has configured the
POUS request signal to these digital inputs
at the factory.
0 ms
Sets the time after which the POUS com-
pleted indication (POUS.22 POUS com-
pleted output) is activated after the POUS
request.
Adjust the default value if necessary.
None
Sets the digital output that indicates the
activity of the POUS function. Active from
the POUS request until the function is ac-
knowledged.
The safety function described in this manual
does not use this digital output.
DO X113:7
Sets the digital output that indicates the
active state of the POUS function (that is,
the motor is stopped and the drive STO is
active). Active after the time defined by
parameter POUS.13 has elapsed from the
POUS request until the POUS request is
removed and the POUS function is acknow-
ledged (automatic acknowledgement is
used, see parameter POUS.02 POUS ac-
knowledgement).
For option +Q950, ABB has configured the
POUS indication signal to this digital output
at the factory. Make sure that this value
corresponds to the actual wiring. See the
circuit diagrams of the delivery.
1)
Sets the diagnostic pulse of digital input
On
X113:3 on or off.
On: The input monitors that it receives test
pulses.
On
1)
Sets the diagnostic pulse of digital input
X114:3 on or off.
On: The input monitors that it receives test
pulses.