Waterite BLACKMAXX RB8 Operator's Manual

Waterite BLACKMAXX RB8 Operator's Manual

Advanced reverse osmosis system

Advertisement

RB8 BLACKMAXX™
Advanced Reverse Osmosis System
OPERATOR'S MANUAL
BLACKMAXX™ RB8 COMPACT MUNICIPAL RO SYSTEMS
THIS MANUAL IS TO BE LEFT WITH THE OWNER OF THE EQUIPMENT FOR
REFERENCE PURPOSES AND TECHNICAL GUIDANCE.
IT IS STRONGLY
RECOMMENDED THAT QUALIFIED DEALER SERVICE PERSONNEL BE CONTACTED
IN THE EVENT OF AN UNKNOWN INTERRUPTION OF SERVICE OR APPARENT
PRODUCT
MALFUNCTION.
AN
ANNUAL
PREVENTATIVE
MAINTENANCE
INSPECTION BY A WATER PROFESSIONAL IS RECOMMENDED TO ENSURE
TROUBLE-FREE AND CONTINUOUS OPERATION.
R3
www.waterite.com

Advertisement

Table of Contents
loading

Summary of Contents for Waterite BLACKMAXX RB8

  • Page 1 IT IS STRONGLY RECOMMENDED THAT QUALIFIED DEALER SERVICE PERSONNEL BE CONTACTED IN THE EVENT OF AN UNKNOWN INTERRUPTION OF SERVICE OR APPARENT PRODUCT MALFUNCTION. ANNUAL PREVENTATIVE MAINTENANCE INSPECTION BY A WATER PROFESSIONAL IS RECOMMENDED TO ENSURE TROUBLE-FREE AND CONTINUOUS OPERATION. www.waterite.com...
  • Page 2: Section 1. Frequently Asked Questions

    Section 1. Frequently Asked Questions Before getting started, take the time to familiarize yourself with your new Waterite system by reading some FAQs listed below. Call us or ask your dealer if you have any other questions about your system’s operation.
  • Page 3 Please contact your dealer or Waterite for information on special application or nanofiltration membranes. 4. TDS: The higher the Total Dissolved Solids in the raw water, the lower the rate of output of product water and the lower the system overall recovery rate.
  • Page 4 Q: What is the standard warranty with the BlackMaxx™ RB8 system? Every BlackMaxx™ RB8 system comes with a standard one-year limited warranty on all parts and shop repair labour, freight excluded. See section 5 in this manual for details on components with limited warranty coverage.
  • Page 5  Manganese: Manganese is a commonly occurring mineral found in ground water. Manganese will leave black, scaly deposits and will eventually foul membranes in concentrations greater than .05 ppm. Manganese must be treated with a manganese greensand filter, regenerated with potassium permanganate. When softeners are used for iron reduction, be sure to fit your softener with a resin bed cleaner to assist in the flushing of iron deposits from the resin bed during backwashing and regeneration.
  • Page 6 Chloride, Fluoride, Bicarbonate, Sulphate, Phosphate, Silica, Total Alkalinity, Total Dissolved Solids, Temperature and Silt Density Index (SDI) Consult your local Waterite Inc. dealer once testing and system requirements have been determined. They can help you to properly size your system for current demands and future expansion.
  • Page 7 Use the pre-treatment summary below to prescribe the necessary pre-treatment where your water analysis indicates parameters outside of the recommended range: Pre-Treatment Summary Chart Recommended Potential Waterite Feed Water Pre-Treatment Solution Effect Models Range Reduced production rate Call your Replace water source <...
  • Page 8 THIS PROCEDURE ALSO APPLIES TO NEW RESIN BED INSTALLATIONS. COLOUR THROW FROM NEW RESIN BEDS MAY DAMAGE OR FOUL RO MEMBRANES. WATERITE DOES NOT RECOMMEND THE USE OF A GRANULAR CARBON CARTRIDGE IN THE PRE-TREATMENT FILTER HOUSINGS SUPPLIED, FOR THE PRIMARY REDUCTION OF CHLORINE.
  • Page 9: Section 3. Installation

    Should the stored water become contaminated for any reason, no cross contamination can occur back to the RB8 system. Consult your Waterite dealer for information and availability on a wide variety of water system components including storage tanks, rep-pressurization pumps, bulkheads, tube, pipe fittings, pressure switches, fittings, UV disinfection systems and float valves.
  • Page 10 3.1. Selecting the system location Position the unit with the clearance shown in Figure 1. The clearance is necessary for removal of the membranes, and maintenance. The frame must be installed level. Figure 1 3.2 Electrical connections All RB8 systems are field certified for electrical compliance. Consult local electrical codes for the electrical disconnect requirements.
  • Page 11 Main control board 120vac Motor power (3 PH) disconnect Field connection terminals Motor starter 120 vac control power Flush valve relay 120vac/24vdc Transformer Figure 2a. Electrical Cabinet Internal On/Off Switch Figure 2b. External Electrical Cabinet Conductivity monitor Manual flush...
  • Page 12 All electrical connections are to be made by qualified personnel, adhering to the local electrical codes. It is recommended that a fused disconnect switch be placed near the unit, for safety purposes. All motors are thermally protected. The level controls should be connected through the cabinet using a liquid tight strain relief connector. This is recommended for all field connections.
  • Page 13 Minimum required inlet flow rates Based on a 50% recovery rate on water <1000 TDS @ 25 degrees Celsius RB820K 27.6 USGPM 104 LPM 1.7 L/sec RB830K 41.0 USGPM 156 LPM 2.6 L/sec RB840K 55.5 USGPM 210 LPM 3.5 L/sec RB860K 83.3 USGPM 315 LPM...
  • Page 14 Permeate Control Valve Permeate Hi TDS Divert Connection Permeate Low TDS To Storage Connection Permeate Flow Sensor Auto Flush Valve Waste Connection CIP Outlet Waste Flow Sensor Waste Control Valve Permeate Sample Port CIP Inlet Permeate TDS Sensor Fig. 3b Back view 3.5 Installing the drain line A line size equal to or larger than your system’s drain line should be used.
  • Page 15 3.7 Installing the filter cartridges and membrane(s) 3.7.1 Cartridge filter Ensure the inlet valve is closed and the system isn’t under pressure. Remove the drain plug located on the front Clamp Handle bottom of the filter housing. Replace the plug once the housing is empty. Remove the filter-housing cap by turning the O-Ring clamp handle counter-clockwise.
  • Page 16 • Insert the end of the element with the protective bag opened into the membrane housing. Remove the bag as you insert the membrane into the housing. Gently push on the membrane end while slowly twisting until the membrane is completely inside the housing. Repeat this process for all membranes.
  • Page 17 ALL ELECTRICAL CONNECTIONS TO THE SYSTEM SHOULD MEET LOCAL CODE AND DONE BY A QUALIFIED ELECTRICIAN. Final set-up of your RO system will be dependent upon the TDS of your feed water. Make sure that you specify the TDS of your feed water at the time the unit is ordered. 4.1 Initial start up and flushing of the system Turn on the feed water valve to the system and check the connection for leaks.
  • Page 18: Section 5: System Maintenance

    To change the cartridge, turn off the system’s power and as a safety precaution, close the water supply to the unit. Repeat Step 3.7.1 from the installation instructions above. Thoroughly flush and clean the filter housings while they are disassembled. Always use Waterite factory cartridges as replacements.
  • Page 19 Waterite carries a complete line of membrane cleaning agents, as well as a Clean-in-Place (CIP) system designed for easy cleaning of the membrane elements, without removing them from the housings. Contact your local representative or call Waterite for pricing and availability. Your RB8 system is already pre-plumbed for a CIP connection.
  • Page 20: Section 6: Trouble Shooting Guide

    Section 6: Trouble Shooting Guide Problem Possible Cause Solution System will not start Disconnect in off position. Turn on. System inlet pressure is too low. Reset alarm-Adjust feed pressure. Low or declining Water supply valve closed. Open valve. permeate production Raw water TDS too high.
  • Page 21 Scaled, perforated or fouled membrane(s). Clean or replace membranes. Fast flush membrane. Pre-treatment system failure. Check pre-treated feed water quality. Raw water quality has changed. Test Raw water. System doesn’t Permeate tank full. Drain Tank start in auto mode Low inlet pressure. Check pre-treatment system water quality.
  • Page 22: Section 7: Spare Parts List

    Section 7: Spare Parts List PRE-FILTERS/MEMBRANE ELEMENTS Part Description Part # Pre-Filter Jumbo Cartridge 10” x 5-Micron Poly-spun HHF405 Pre-Filter Jumbo Cartridge 20” x 5-Micron Poly-spun HHF905 Pre-Filter Jumbo Cartridge 30” x 5-Micron Poly-spun HHF1705 Membrane 8” BlackMaxx RO-SXL BME8040SXL INSTRUMENTATION Part Description Part #...
  • Page 23: Performance Log

    Section 9: Performance Log RB8 BLACKMAXX Date Feed System Permeate Feed Water Permeate Reject Permeate Waste Pressure Pressure Flow Meter Flow Meter Totalizer Totalizer...
  • Page 24 Date Feed System Permeate Feed Water Permeate Reject Permeate Waste Pressure Pressure Flow Meter Flow Meter Totalizer Totalizer...
  • Page 25: Section 10: Appendix

    Section 10: Appendix 10.1 Temperature correction factors The following is meant as a guide for determining the output of your BlackMaxx RB8 system. Locate your model number, and then look for the approximate temperature of your feed water. This will give the estimated output of your system.