Download Print this page

Siemens SIMATIC ET 200S 4DI DC24V ST Manual page 11

Distributed i/o digital electronic module

Advertisement

Properties
1.1 Digital electronic module 4DI DC24V ST (6ES7131-4BD01-0AA0)
Rated supply voltage (from the power module)
Reverse polarity protection
Electrical isolation
Between the channels
Between the channels and backplane bus
Permissible potential difference
Between the different circuits
Insulation test voltage
Current consumption
From supply voltage
Power dissipation of the module
Status display
Diagnostics function
Output voltage
With load
Output current
Rated value
Permitted range
Input voltage
Rated value
For signal "1"
For signal "0"
Input current
At signal "1"
Input delay
At "0" to "1"
At "1" to "0"
Input characteristic curve
Connection of 2-wire BEROs
Permitted bias current
10
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Voltages, currents, potentials
24 VDC
Yes
No
Yes
75 VDC / 60 VAC
500 VDC
Dependent on the sensor
Typically 0.7 W
Status, interrupts, diagnostics
Green LED per channel
No
Sensor power supply output
Min. L+ (-0.5 V)
500 mA
0 to 500 mA
Data for selecting a sensor
24 VDC
15 V to 30 V
-30 V to 5 V
Typ. 7 mA (for 24 V)
Typ. 3 ms (2.0 to 4.5 ms)
Typ. 3 ms (2.0 to 4.5 ms)
According to IEC 61131, Type 1
Supported
Max. 1.5 mA
Digital electronic module 4DI DC24V ST (6ES7131-4BD01-0AA0)
Manual, 04/2007, A5E01077099-01

Hide quick links:

Advertisement

loading

This manual is also suitable for:

6es7131-4bd01-0aa0